Locating furnace – Vogelzang International 1500 User Manual

Page 6

Advertising
background image

Page 6

/

NORSEMAN™ 1500/2500 FuRNAcE

VGZ-018 / 051809.0

locAtiNg FURNAcE

NOTICE: Installation of this furnace must be done
by a qualified heating equipment installer.

C A U T I O N : F U R N A C E U N I T S A R E
hEAvY - APPROxImATELY 450-550 LBS.
mAkE SURE YOU hAvE PROPER EqUIP-
mENT AND OR SUFFICIENT mANPOwER TO
PREvENT INjURY whEN DELIvERINg AND
LOCATINg FURNACE UNITS.

1. The furnace must be placed on solid concrete or

masonry floor.

NOTE: To reduce weight during in-

stallation remove parts from inside the firebox.
Additional weight reductions can be obtained
by removing the fire brick. make note of position
so they are returned to the same positions.

CAUTION: DO NOT OPERATE ThIS APPLIANCE
wITh CRACkED OR mISSINg FIREBRICkS.

2. The furnace should be located in the same

room as the central heating system, as close as
possible but no closer than 6˝ to the central sys-
tem. (See figures 16 – 23). Make sure to allow for
maintenance clearances of the central heating
system.

3. Obser ve the clearances to combustible

materials as listed and shown in figures 1, 2 & 3.

minimum Clearances to Combustible Surfaces

Front: 48 in. Side: 16 in. Back: 26 in.

Chimney Connectors: 18 in. Plenum to wall-

studs, joists or finished wall or ceiling: 2 in.

4. The furnace

mUST have its own flue. DO NOT

CONNECT ThIS UNIT TO A ChImNEY FLUE
SERvINg OThER APPLIANCES.

5. Install furnace pipe, elbows, and thimble as

required, utilizing either a recently cleaned and
inspected 6˝ masonry chimney or a 6˝ i.d. listed uL
103 HT chimney. NOTE: A barometric draft regula-
tor may be necessary if the chimney draft is found
to be excessive.

wARNINg: RISk OF FIRE. DO NOT OPERATE
wITh FLUE DRAFT ExCEEDINg 0.05˝ wATER
COLUmN (0.1 Pa).

6. use 6˝ diameter minimum 24 MSG black or 26 MSG

blue steel furnace pipe to connect to the chimney.
DO NOT use galvanized furnace pipe. Secure pipe
sections with three (3) sheet metal screws in each
furnace pipe and/or elbow joint to firmly hold the
pipe sections together.

7. R e c h e ck c l e a ra n c e s f r o m t h e f u r n a c e,

connector furnace pipe, and corner clearanc-
es using the illustrations in figures 1 – 3 and
your local building codes or fire protection
ordinances.

NOTE: A studded wall faced with brick or stone
must be considered a combustible surface.

8.

DO NOT INSTALL ThIS FURNACE IN A mOBILE
hOmE, mANUFACTURED hOmE, TENT OR TRAILER.
NO ExCEPTIONS!

(HUD Federal Standard: 24 CFR Ch.XX)

9. The clearances provided are minimum dimen-

sions determined by the manufacturer’s testing
facility in accordance with u.S. Test Standard
uL 391-06. Installation of this furnace must
comply with the latest edition of NFPA 211 for re-
duced clearances and/or your local building code
rulings (use whichever minimum dimensions are
LARGEST).

Fig. 1 – Top View

Minimum Clearances from Combustible Surfaces

Fig. 2 – SiDe View

Minimum Clearances from Combustible Surfaces