Specifications, Dimensional drawings, Ordering information – Watlow Electric E-Safe II User Manual

Page 2: Product rating curve, How to contact watlow

Advertising
background image

Ordering Information

E S 2 _ - _ _ _ _ - _ _ _ _

E-SAFE II = Hybrid Power Switch
Number of Poles
1

= 1 pole

2

= 2 poles controlled

3

= 3 poles controlled

Load Voltage
1

= 100 to 120VÅ(ac)

2

= 200 to 240VÅ(ac)

3

= 230/277VÅ(ac) [400/480VÅ(ac) with

wye/star, neutral connected to center
required]

Command Signal Voltage
LV = Low voltage 3 to 24VÎ(dc) or 24VÅ(ac)
HV = High voltage 100 to 240VÅ(ac)

+10/-15%, [85 to 264VÅ(ac)]

Future Option

Future Option

Custom Parameters
000 = Standard product
Any three letters or numbers = cosmetic options

Specifications

Output voltage

200/240VÅ(ac) +10/-15%, 50/60Hz, 100/120VÅ(ac)
+10/-15%, 50/60Hz

Output amperage

Up to 35A single, dual and three-phase

Operating environment

0 to 70°C (32 to 158°F) operating temperature

0 to 90% RH, non-condensing

Operational life: four million switching cycles

Installation category III, pollution degree 2

Control mode

NO-ARC hybrid contactor

Input command signal

3 to 32VÎ(dc), 24VÅ(ac) +20/-20%, off state

≤2.7VÎ(dc)

100 to 240VÅ(ac) +10/-15%, [85 to 264VÅ(ac)]
Note: On the 100 to 240VÅ(ac) input models, do not use
a RC snubber on the E-SAFE II relay input or the
temperature control command signal output.

LED indicator light

Built in LED assists in trouble shooting; LED "off" indicates
relay(s) are open, LED "on" indicates relay(s) are closed.

Input command signal terminals

1

4

in. fast on appliance

Line and load terminals

No. 10 screw will accept ring or spade,
6.35 mm (

1

4

in.) x 10-32

Mounting

Back panel mount, horizontal or vertical mounting options

6.35 mm
(0.25 in.)

97.03 mm

(3.82 in.)

82.55 mm

(3.25 in.)

140.72 mm

(5.54 in.)

48.51 mm
(1.910 in.)

14.88 mm
(0.586 in.)

46.99 mm

(1.85 in.)

23.88 mm

(0.94 in.)

0 0

60

Amperage

Dimensional Drawings

Ambient

Temperature

°C

5

10

15

20

25

30*

35

65

70

55

50

45

40

35

30

25

UL

®

Conditions of Acceptability

Applications must be tested as described below for specific wire
insulation or specific wire gauge sizes. Tests shall be performed in
the end application under worst case operating conditions.
Test Procedure

A. Monitor temperatures of terminals, using thermocouples between the

ring terminal and connectors L1, L2 or L3. The temperature must not
exceed 95°C (203°F).

B. Monitor temperatures of wire insulation, using a thermocouple located

three inches from the connector. The temperature must not exceed
the insulation rating of the wire.

*30A is maximum rating when operating above 240VÅ(ac).

Warning: Thermocouples attached to terminals will be at load voltage

potential, measurements need to be taken with isolated equipment or
isolate the sensor from terminal with suitable insulation.

8

AWG

90°C

Wire

10

AWG

90°C

Wire

6 AWG
90°C Wire

These ratings apply to
3-phase units with cycle
times of 30 seconds or
more. Consult the
factory for 1- and
2-phase unit ratings.

Product Rating Curve

To be automatically connected to the nearest North American Technical Sales Office:

1-800-WATLOW2 • www.watlow.com • [email protected]

International Technical Sales Offices:

Australia, +61-3-9335-6449 • China, +86-21-3950-9510 • France, +33 (0) 3073-2425 •

Germany, +49 (0) 7253-9400-0 • Italy, +39 (0) 2 458-8841 • Japan, +81-3-3518-6630 • Korea, +82-2-575-9804 • Malaysia, +60-3-7980-7741 •
Mexico, +52 (442) 217-6235 • Shanghai, +86-21-3950-9504 • Singapore, +65-6777-1266 • Spain, +34 91 675 1292 • Sweden, +46 35-27-11-66 •
Taiwan, +886-7-288-5168 • United Kingdom, +44 (0) 115-964-0777

Advertising