Wing Enterprises IOMWDF-1 User Manual

Page 15

Advertising
background image

15

Symptom

Possible Cause

Field Test

Remedy

E. continued

F. Incorrect

Maximum or
Minimum
Discharge Air
Temperature.

G. Continuous High

Fire (Electronics
OK).

H. Continuous High

Fire (Electronics
Problem).

I. Incorrect High Fire

J. Continuous

Maximum Discharge
Air Temperature.

K. Burned out

Transformer. No
Voltage to Amplifier.

3. Follow procedures outlined

in “Preliminary Circuit
Analysis” in Section IX.

1. Compare sensed

temperature reading at
TS144 with average
discharge air temperature.

2. Follow procedures outlined

in “Preliminary Circuit
Analysis” in Section IX.

1. Remove bottom plate and

inspect valve and seat.

2. Inspect. Plunger should

be smooth and clean and
operate freely in solenoid
sleeve.

1. Measure resistance per

item C3.

1. Read inlet pressure at valve

using manometer with
heater operating at full fire.
Pressure should be at least
equal to the sum of: outlet
pressure setting and
pressure drop of the valve
plus 1.0” W.C.

2. Read outlet pressure using

manometer and compare
with the pressure stated
on the specification plate.

1. Follow procedures outlined

in “Preliminary Circuit
Analysis” in Section IX.

2. Measure resistance per

item E2.

3. Follow procedures outlined

in “Preliminary Circuit
Analysis” in Section IX.

1. Measure resistance per

item B1.

3. If proper action is obtained,

first check item E2.
Recalibrate if necessary.

1. Move TS144 to location

where average temperature
can be sensed.

2. If proper temperatures are

not observed, refer to
Discharge Air Temperature
calibration procedures.

1. Clean, replace valve and/or

seat if necessary.

2. Clean, or if necessary,

replace plunger

1. If readings are incorrect,

replace the TS144 or repair
wiring.

1. Increase inlet pressure if

possible or change to larger
valve. Consult factory
about possibility of using
special spring to reduce
pressure drop on selected
installations.

2. See Valve Adjustments in

Section IX.

1. If amplifier is proven at

fault, install replacement
amplifier.

2. If reading is incorrect,

replace T244,
TS244/TD244 or repair
wiring.

3. If proper action is obtained,

first check item J2.
Recalibrate if necessary.

1. If proper resistances are

not observed, replace
modulator head or repair
wiring.

Control circuits external to Series 44 can cause burner malfunction. Always check manual valve to be

certain gas is on, and check limit controls for normal operation.

3. Incorrect space

temperature calibration.

1. Improper TS144

location.

2. Incorrect discharge

air temperature
calibrations.

1. Foreign material

holding valve open.

2. Plunger jammed.

1. Open circuit in TS144.

1. Inlet pressure too low.

2. Incorrect outlet

pressure adjustment.

1. Faulty amplifier.

2. Open circuit in T244

or TS244/TD244.

3. Incorrect space

temperature calibration.

1. Short in modulator coil

circuit.

TROUBLESHOOTING GUIDE

Series 44 Room Temperature Control continued

Reproduced with permission from Maxitrol® Company

Advertising