WIRING

SETTING THE DIAL

All wiring must conform to local and national electrical codes and ordinances.
Connect in accordance with wiring diagrams provided by the equipment manufacturer. If none are provided, the following repre-
sents a typical installation.

The movable indicator (D) points to the temperature at which
the compressor starts. The fixed indicator (B) points to the
temperature at which the compressor will stop. The difference
between these two indicators is the differential. Follow these
instructions to set the dial:

1. Insert a screwdriver in the adjusting slot (A) and turn the

dial until the fixed indicator (B) points to the temperature at
which the compressor is to stop.

2. Turn the differential adjusting screw (C) until the movable

indicator (D) points to the temperature at which the com-
pressor is to start.

Temperature

control

Low

temperature

limit

High side

pressure control

(if used)

To

Compressor

Motor

Line

L1

L2

Note: Make L1 “HOT” on

120V installation

Circuit showing temperature control control-
ling compressor directly.

Temperature

control

Low temperature

limit

Suction

pressure

control

High side

pressure

control

Motor

starter

Solenoid

refrigerant

valve

To

Compressor

Motor

Line

L1

L2

Note: Make L1 “HOT” on 120V installation

Circuit showing temperature control to open and close refrigerant valve. Suction
pressure control starts and stops compressor through motor starter.

"B" Fixed indicator

(cut-out point)

"C" Differential

adjusting screw

"D" Movable indicator

(cut-in point)

"A" Adjusting

slot

Controls with one circuit (two terminals)

Controls with two circuits (three terminals)

BLUE

RED

WHITE

240V

22.2A

22.2A

LOAD CONDITIONS

MAXIMUM ALLOWABLE RATING

Full Load

Locked Rotor

120V

7.4A

7.4A

120V

44.5A

44.5A

240V

3.7A

3.7A

Load between Blue and Red
terminals must not exceed:
Load between Blue and White
terminals must not exceed:

To

Additional

Units

B R

W

B R

W

Valve

No. 2

Valve

No. 1

Blue
White
Red

To

Compressor

Motor

Line

L1

L2

Note: Make L1 “HOT” on

120V installation

Temperature

control

Temperature

control

Low

temperature

limit

Low

temperature

limit

This diagram shows a typical two-circuit
application. Several zones receive re-
frigeration from the same compressor,
but each zone requires its own solenoid
refrigerant valve, temperature control and
limit control.

Typical Refrigeration Pump Down Circuit

The blue terminal is common. The table below shows the maxi-
mum load allowed between terminals.