Start-up – Whirlpool Indirect-Fired Water Heater User Manual

Page 8

Advertising
background image

7

Figure 7: Wiring Diagram – MI/MIH

Figure 8: Wiring Diagram – WBV, EC and SC less Tankless

1. General

a. Open hot water faucet when filling or draining Peerless Partner.

b. The Peerless Partner thermostat has three markings: Warm (120°F), Normal (140°F), and Hot (160°F).

The thermostat is adjusted to its lowest temperature position when shipped from the factory.

2. Fill tank and domestic water piping.

3. Adjust Peerless Partner thermostat to 119°F, or in accordance with authority having jurisdiction. Adjust

mixing valve (if used) to desired temperature.

4. Follow manufacturer’s instructions to start-up boiler. Set boiler limit at least 20°F above Peerless Partner

thermostat setting. For boiler limit with low limit, set temperature to lowest setting. For boiler limits with
adjustable differential, set differential to 10-15°F range.

5. Operate boiler until Peerless Partner thermostat satisfied. Measure domestic water temperature at hot

water faucet. See Paragraph 3 above.

6. Draw hot water and allow Peerless Partner to operate through several recovery cycles to verify proper

operation.

Start-up

Advertising