INSTALLATION (continued)

WARNING:

Electric Shock hazard

All servicing requiring access to non-insulated electrical components must be
performed by a factory authorized technician.
DO NOT open any access panel which requires the use of tools. Failure to follow this
warning can result in severe electrical shock.

CAUTION:

Risk of
Damage

DO NOT connect or energize
this appliance until all
installation instructions are
read and followed. Damage
to the appliance will result if
these instructions are not
followed.

CAUTION:

Electrical Shock
Hazard

The ground lug of F-886
fryers must be connected to
a suitable building electric
ground.

IMPORTANT:

Damage due to being
connected to the wrong
voltage or phase is NOT
covered by warranty.

F-886 FRYER ELECTRICAL INSTALLATION

F-886 fryers must be connected directly to an appropriately sized
electrical circuit. Conduit and strain relief must be provided by the
electrician.

F-886 fryers are not rated for single phase operation at 208VAC.

Single phase F-886 fryers require a 240VAC 60 amp 1ø circuit with
ground;

Three phase F-886 fryers require a 208VAC or 240VAC 3ø, 40 amp
circuit with ground,

FRYERS ARE SHIPPED FROM THE FACTORY WIRED FOR 3ø.
Conversion to single phase is the responsibility of the electrician.