Installation, Continued next page – Wayne-Dalton Z-WAVE WDTC-20 User Manual

Page 11

Advertising
background image

11

Step 4: Wiring Information (continued)

IMporTanT!

additional Wiring notes:

•

For heat pumps with O and B both present, connect O wire to O terminal and B wire to C terminal (noTE:

This is typically for Trane Heat Pump products only.) Do not connect B wire to B terminal as it may

damage the 24VAC power system.
•

For LENNOX Pulse systems, please contact customer support or contact your HVAC professional for specific

information regarding installing the Z-Wave

®

Enabled Thermostat with your system.

•

Use 18- to 22-gauge thermostat wire.

•

Your Z-Wave® enabled thermostat must have a C wire (electrical power) and cannot operate from batteries

alone. Batteries are for back up only.
•

If you are unsure of how to connect your system, please call customer support for additional information or

contact an HVAC professional.
•

If you have 2 large wires (12 or 14 gauge or if it is bigger than paper clip wire) or know that your system

operates on line voltage, immediately stop, re-install your existing thermostat and contact customer support.
The Wayne-Dalton Z-Wave

®

Enabled thermostat operates on 24 Volts AC power only.

Jumper reference Guide

The number below corresponds to the bubble number above.

Jp5 --

Fan Control: a)

no Fan -No fan control even with switch on front of thermostat (RARE.)

(No jumper)

b)

ELECT - Fan is controlled from thermostat.

(Jumper on top 4 pins)

c)

GaS - Fan is controlled by furnace.

(Jumper on bottom 4 pins)

Jp3 --

Heat Pump Type: a)

oFF - No heat pump system present (Conventional HVAC System)

( No Jumper)

b)

on - Bypasses heat pump 1st stage and immediately triggers auxiliary heating.

(Eliminates time delay for effectively heating homes located in colder climates.)

(Jumper on top 4 pins)

c)

Heat pump - Normal heat pump setting to activate both stages.

(Jumper on bottom 4 pins)

Jp4 --

Power: a)

rC-rH Connected - For single transformer systems.

(Jumper on both pins)

b)

rC-rH Separate - For systems with a separate transformer for A/C and heat.

(No Jumper)

Jp1 --

Celsius/Fahrenheit: a)

°C - Thermostat will display in degrees Celsius.

(Jumper on both pins)

b)

°F - Thermostat will display in degrees Fahrenheit.

(No Jumper )

Jp2 --

Heat Pump Auxiliary Type: a) Fossil fuels - Natural gas, propane, or oil auxiliary system.

(Jumper on both pins)

b) Elect - Electric auxiliary system.

(No Jumper)

reset --

Reset Button - Always press the reset button after changing jumper settings.

noTE:

Unused jumpers may be stored by attaching them to a single pin.

reset

Installation

JP2

JP1

Continued Next Page

AUTO

ON

FAN

HEAT

COOL

SAVE

ENERGY

NORMAL

RESET

COOL

JP4

JP3

JP5