Electrical installation, Important, Danger – Wells WVOC-G136 User Manual

Page 11: Installation (continued)

Advertising
background image

SERVICE TECHNICIAN INSTALLATION NOTES


An Ansul® technician must charge and arm the fire suppression system
before the ventilator blower will operate. See page 10.


Installation and start up must be performed by an Authorized
Installation Company.


Installer must complete the WARRANTY REGISTRATION form, and
record appliance installation particulars on the CUSTOMER SERVICE
DATA
form in this manual.


Certain codes require cooking equipment to be restrained with a
RESTRAINT DEVICE. It is the RESPONSIBILITY OF THE
INSTALLER to check with the AUTHORITY HAVING JURISDICTION,
in order to ascertain the applicability of this requirement to THIS
SPECIFIC EQUIPMENT INSTALLATION. Any restraint device must
allow access to the back and sides of the unit to provide for servicing
and maintenance, and must not interfere with the operation of the FIRE
SUPPRESSION SYSTEM.

ELECTRICAL INSTALLATION


This appliance must be installed by a licensed electrician in compliance
with all applicable Federal, State and local codes and ordinances.

Electrical connections, contactor and ground lug are accessible by
removing the bottom rear panel.

Refer to the nameplate on the cooking appliance to verify the
ELECTRICAL SERVICE POWER. Voltage and phase must match the
nameplate specifications, and available electrical service amperage
must meet or exceed the specifications listed on page 1. Incoming
wiring must comply with National Electrical Code specifications.

All universal hood appliances ship from the factory wired 3ø and include
a 3ø cordset.


This appliance is NOT approved for 1ø operation.

IMPORTANT!

Verify that this VENTILATOR
and food cooking equipment
installation is in compliance
with the specifications listed
in this manual, with local
code requirements, and in
accordance with N.F.P.A 96
(THE STANDARD FOR
VENTILATION CONTROL
AND FIRE PROTECTION
OF COMMERCIAL
COOKING OPERATIONS
-
current edition).

THIS IS THE

RESPONSIBILITY

OF THE INSTALLER


DANGER:

ELECTRIC
SHOCK
HAZARD


ELECTRIC CONNECTIONS
MUST BE MADE BY A
LICENSED ELECTRICIAN
Electrical shock will cause
death or serious injury.


NOTE: This appliance
requires a dedicated 60 Amp
electrical branch circuit
protection.

IMPORTANT:
Contact a licensed electrician
to install and connect
electrical power to the
appliance.


IMPORTANT:
Damage due to being
connected to the wrong
voltage or phase is NOT
covered by warranty.

INSTALLATION (continued)

9

509 3059

36 O

p

M

W

V

OC-G

136

Advertising