M U L T I P L E C O O K T O P I N S T A L L A T I O N

IMPORTANT NOTE: If the steamer module is
to be used with a combination of additional
cooktop units or modules with a filler strip,
the cut-out width is calculated by adding the
corresponding units' cut-out dimensions plus
32 mm for each additional unit.

When multiple units are installed side by side,
each unit must have its own separate recom-
mended electrical circuit.

When two or more modules are installed
together, an integrated module filler strip
(IFILLER/S) is recommended. Contact your
Wolf dealer for information on accessories.

IMPORTANT NOTE: Review specific
installation instructions for product to product
capabilities.

W O L F

S T E A M E R M O D U L E

I N S TA L L AT I O N

S P E C I F I C A T I O N S

D R A I N C O N N E C T I O N

IMPORTANT NOTE: The steamer module
must be installed with a drain connection and
access to the drain through the base cabinet.

For the drain connection, the 16 mm outlet
from the valve will accept a drain hose that
must flow downward to and tie into an
existing sink drain, or a separate drain with a
freefall may be installed. Following local
building codes; your plumber will dictate how
to plumb the unit. As a third option, the
consumer will supply a heat resistant bucket
for drainage in the location of the drain outlet.
Refer to the illustration on page 7 for location
of the drain outlet.

64 mm

min

FRONT OF COUNTERTOP

489 mm

CUT-OUT

DEPTH

743 mm

TWO MODULES WIDTH

1130 mm

THREE MODULES WIDTH OR

1124 mm

/762 mm COOKTOP AND ONE MODULE

1518 mm

FOUR MODULES WIDTH OR

1511 mm

/762 mm COOKTOP AND TWO MODULES OR

1276 mm

/914 mm COOKTOP AND ONE MODULE

356
mm

CUT-OUT

WIDTH

Countertop cut-out dimensions for installation of multiple cooktops

This steamer module must be installed
at least 381 mm away from a Wolf fryer
module, as contact between water and hot
oil may cause burns from steam and hot oil.

If there is no fixed drain connection, use a
heat-resistant receptacle with a minimum
7.6 L capacity. The doors of the base
cabinet must be locked.