On some installations it may be desirable
to install an independent hanger for the
level control switches to avoid possible
hang ups on the pumps, piping, valves,
etc. Float hangers are available from
Zoeller Company on Catalog Sheet
FM0526 or can be fabricated from stan-
dard pipe and fi ttings.

SUGGESTED METHODS OF FLOAT INSTALLATION

TYPICAL FLOAT HANGER ON CONCRETE PITS

OR SEPTIC TANK RISERS

TYPICAL FLOAT HANGER ON STEEL COVER PITS

ACCESS COVER

STANDARD PIPE

FLANGE

PVC OR LIGHT WEIGHT

STAINLESS STEEL PIPE

PEAGRAVEL

TYPICAL FLOAT HANGER ON CONCRETE PITS

OR SEPTIC TANK RISERS

10-1457 FLOAT TREE

WITH 3 FLOATS SHOWN

SK1217

SK1218

RECOMMENDED INSTALLATION FOR ALL APPLICATIONS

All installations must comply with all applicable electrical and plumbing codes, including, but not limited to, National Electrical Code, local, regional, and/or state plumbing
codes, etc. Not intended for use in hazardous locations.

(1) Electrical wiring and protection must be in accordance with National

Electrical Code and any other applicable state and local electrical

requirements.

(2) Install proper Zoeller unicheck (combination union and check valve),

preferably just above the basin to allow easy removal of the pump for

cleaning or repair. On sewage, effl uent or dewatering, if high head or

below cover installation is required use 30-0164 on 1½" pipe, 30-0152

on 2" pipe and 30-0160 on 3" pipe. See (4) below.

(3) All installations require a basin cover to prevent debris from falling into

the basin and to prevent accidental injury.

(4) When a Unicheck is installed, drill a 3/16" dia. hole in the discharge

pipe even with the top of the pump. NOTE: THE HOLE MUST ALSO

BE BELOW THE BASIN COVER AND CLEANED PERIODICALLY.

(High Head unit see #3 under “Caution” on front page). Water stream

will be visible from this hole during pump run periods.

(5) Securely tape or clamp power cord to discharge pipe, clear of the fl oat

mechanism(s).

(6) Use full-size discharge pipe.

(7) Basin must be in accordance with applicable codes and

specifi cations.

(8) Pump must be level and fl oat mechanism(s) clear of sides of basin

before starting pump.

(9) Basin must be clean and free of debris after installation.

(10) Gate Valve or Ball Valve to be supplied by installer and installed

according to any and all codes.

(11) Locate fl oat switches as shown in sketches. The best place for the

“off” point is above the motor housing and positioned 180° from the

inlet. Never put “off” point below discharge on pump (Sewage &

Effl uent only). NOTE: FOR AUTOMATIC PUMPS, USE

DEWATERING INSTALLATION SKETCH.

(12) Gas tight seals required to contain gases and odors.

(13) Vent gases and odors to the atmosphere through vent pipe (Sewage

& Dewatering only).

(14) Install Zoeller Pump Stand (Model 10-2421) under pump to provide a

settling basin. (Effl uent & Dewatering only.)

For Effl uent Only:

(15) Wire pump to power through a Zoeller watertight junction box or

watertight splice. NOTE: Watertight enclosure is a must in damp

areas. See No. 8 on front page of FM0732.

(16) Refer to SSPMA Effl uent Sizing Manual for determining “on” - “off”

switches.

(17) Septic tank risers must be used for easy pump and fi lter access.
NOTE: Double seal pumps offer extra protection from damage caused by

seal failure.

TYPICAL SEWAGE INSTALLATION

SK290

Always refer to

FM0551 and/or

SSPMA recom-

mended sewage

pump installation

and maintenance.

TYPICAL EFFLUENT INSTALLATION

SK291

See FM0531,

FM0732 & FM1420

for alarms, controls

& junction boxes

TYPICAL DEWATERING INSTALLATION

SK292

See FM0531, FM0732 & FM1420 for alarms,

controls & junction boxes