York SUNLINE 2000 BP 072 User Manual

Page 22

Advertising
background image

036-21630-001-B-0904

22

Unitary Products Group

TABLE 11: PHYSICAL DATA

MODELS

BP 072

EVAPORATOR

BLOWER

Centrifugal Blower (Dia. x Wd. in.)

12 X 10

Fan Motor HP (Belt Drive)

1 1/2

EVAPORATOR

COIL

Rows Deep

4

Fins Per Inch

13

Face Area (Sq. Ft.)

5.1

CONDENSER

FANS

Propeller Dia. (in.)

24

Fan Motor Hp

1/2

Nom. CFM

4500

CONDENSER

COILS

Rows Deep

2

Fins Per Inch

18

Face Area (Sq. Ft.)

17.1

COMPRESSOR

(Qty. Per Unit)

Scroll Type

1

AIR

FILTERS

Quantity Per Unit (15” X 20” X 1” or 2“)

2

Quantity Per Unit (14” X 25” X 1” or 2“)

1

Total Face Area (sq. ft.)

6.6

CHARGE

Refrigerant 22

(lbs./oz.)

12/0

TABLE 12: ELECTRIC HEAT CORRECTION

FACTORS

NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTI-

PLIER

208

208

1.00

240

230

0.92

480

460

0.92

600

575

0.92

TABLE 13: VOLTAGE LIMITATIONS

1

POWER SUPPLY

VOLTAGE

MIN.

MAX.

208/230-3-60

187

253

460-3-60

414

506

575-3-60

518

506

1. Utilization Range “A” in accordance with ARI Standard

110.