SUPPLEMENTAL INSTALLATION INSTRUCTIONS

MODEL H4CE180A40 (380V-3-60 Hz Electrical Supply)

SPLIT-SYSTEM CONDENSING UNITS (EXPORT)

035-17392-000 REV. A (0401)

Subject to change without notice. Printed in U.S.A.

035-17392-000 REV. A (0401)

Copyright

©

by Unitary Products Group 2000. All rights reserved.

Supersedes: 035-17318-000 Rev. A (10/00)

Unitary

5005

Norman

Product

York

OK

Group

Drive

73069

Scope

This installation Instruction Supplement provides information specific to Model H4CE180A40. For all other
information regarding the installation and operation of this unit, refer to Installation Instruction Form 035-17384-000.

Approvals

As unit is for Export, it is not certified by ETL or CGA.

NOTES:1. Condenser Fan Motors are supplied by one (1) autotransformer (p/n 025-32756-000) used to elevate

380 volt supply to 475 volt. Full load Amp rating at 460-3-60 supply is 2.4 amp rating at 380 volt supply
terminals of autotransformer is 2.6.

2.

Dual Element time delay type fuses or HACR circuit breakers. Refer to NEC/NFPA No. 70,
Articles 440-11 & 12 for information on disconnect size.

TABLE 3: Electrical Data

Model

HCE

Voltage

Code

Power

Supply

Compressor

Condensing Fan

Minimum Cir-
cuit Ampacity

Maximum Fuse Size.

Amps (See Note 2)

Sys. #1

Sys. #2

HP

FLA (See Notes)

RLA

LRA

RLA

LRA

180

40

380-3-60

16.7

123

16.7

123

1.0 EA.

2.5 EA.

42.6

50

®