CLEARANCES

All units require particular clearances for proper operation
and service. Refer to Table 6 for clearances required for con-
struction, servicing, and proper unit operation.

NOTE:

A one-inch clearance must be provided between
any combustible material and the supply ductwork
for a distance of 3 feet from the unit.

Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet, combustion
air inlet or vent outlets.

FIGURE 8 -

UNIT DIMENSIONS

F o r B a s e r a i l

D i m e n s i o n s

S e e D e t a i l A

8 9

( 2 2 6 0 )

2 7

( 6 8 5 )

5 9

( 1 5 0 0 )

5 0 - 3 / 4

( 1 2 9 0 )

4 - 1 / 4

( 1 1 0 )

1 7 - 3 / 1 6

( 4 3 5 )

2 4 - 3 / 1 6

( 6 1 5 )

3 0 - 3 / 1 6

( 7 6 5 )

P o w e r

E n t r y

Ø 2 - 1 / 2

( 6 5 )

3 0 - 1 1 / 3 2

( 7 7 0 )

C o n t r o l

E n t r y

Ø 7 / 8

( 2 2 )

P o w e r

E n t r y

Ø 2 - 1 / 2

( 6 5 )

L E F T

F R O N T

6 - 3 / 1 6

( 1 5 5 )

C o n v e n i e n c e

P o w e r

O u t l e t

E n t r y

Ø 7 / 8

( 2 2 )

N O T E : ( x x x ) i n d i c a t e s d i m e n s i o n s

g i v e n i n m i l l i m e t e r s

F o r D r a i n

D i m e n s i o n s

S e e D e t a i l B

TABLE 6: UNIT CLEARANCES

*

*.

In inches and millimeters, in.(mm).

Top

†

†.

Units must be installed outdoors. Overhanging structure or
shrubs should not obstruct condenser air discharge outlet.

72 (1830)

Right

12 (305)

Front

36 (915)

Left

36 (915)

Rear

‡

‡.

To remove the slide-out drain pan, a rear clearance of 60”
(1525 mm) is required. If space is unavailable, the drain pan
can be removed through the front by separating the corner
wall.

36 (915)

Bottom

**

**.

Units may be installed on combustible floors.

0 (0)

3 - 3 / 4

( 9 5 )

3 - 9 / 1 6

( 9 0 )

2 - 3 / 8

( 6 0 )

DETAIL A

5 - 3 / 8

( 1 3 5 )

DETAIL B