TABLE 7: HEATING APPLICATION DATA 7-1/2 TON HP HEAT (IMPERIAL)
CFM
ID DB
CAP & kW
OUTDOOR TEMPERATURE (°F) (72% RH)
-10
0
10
20
30
40
50
60
2250
55
MBH
26.1
31.8
38.7
47.1
57.3
69.8
85.0
103.6
KW
5.0
5.4
5.8
6.3
6.7
7.1
7.5
8.0
70
MBH
22.7
28.3
35.2
43.6
53.9
66.4
81.6
100.2
KW
5.8
6.2
6.6
7.0
7.5
7.9
8.3
8.7
80
MBH
18.9
24.6
31.5
39.9
50.1
62.6
77.8
96.4
KW
6.2
6.6
7.0
7.4
7.9
8.3
8.7
9.1
3000
55
MBH
29.2
34.9
41.8
50.2
60.4
72.9
88.2
106.7
KW
4.9
5.3
5.8
6.2
6.6
7.0
7.5
7.9
70
MBH
25.8
31.4
38.3
46.7
57.0
69.5
84.7
103.3
KW
5.7
6.1
6.5
7.0
7.4
7.8
8.2
8.7
80
MBH
22.0
27.7
34.6
43.0
53.2
65.7
81.0
99.5
KW
6.1
6.5
6.9
7.3
7.8
8.2
8.6
9.0
3750
55
MBH
34.0
39.6
46.5
54.9
65.2
77.7
92.9
111.5
KW
5.0
5.5
5.9
6.3
6.7
7.2
7.6
8.0
70
MBH
30.5
36.2
43.1
51.5
61.7
74.2
89.5
108.0
KW
5.8
6.2
6.7
7.1
7.5
7.9
8.4
8.8
80
MBH
26.8
32.4
39.3
47.7
58.0
70.5
85.7
104.3
KW
6.2
6.6
7.0
7.5
7.9
8.3
8.8
9.2
THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.