Dimensions (english) ycal0024sc - ycal0034sc – York YCAL0080SC User Manual

Page 40

Advertising
background image

YORK INTERNATIONAL

40

DIMENSIONS (ENGLISH)

YCAL0024SC - YCAL0034SC

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated
performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated
below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize
operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance
degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended mini-
mum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'; top – no obstructions allowed; distance
between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.

LD03846

Installation

* Refers to Model YCAL0030SC

** Refers to Model YCAL0034SC

Advertising
This manual is related to the following products: