Troubleshooting – York R123 User Manual

Page 140

Advertising
background image

YORK INTERNATIONAL

140

FORM 160.55-O1 (604)

TABLE 1 – CAUSES OF NOR MAL AND SAFE TY SYS TEM SHUT DOWNS IN AC COR DANCE WITH THE

CONTROL CENTER DISPLAY - CONTINUED

SHUTDOWN CAUSE CON TROL CENTER DISPLAY GOVERNING CONTROL FUNCTION

DAY OF TIME CAUSE OF METHOD OF DESCRIPTION OPERATING POINT

WEEK OF DAY SHUTDOWN RESTART ON RISE ON FALL

MON. 10:00 AM Oil Pressure High Oil Pressure 60 PSID 59 PSID
Transducer Error Transducer or Low
Oil Pressure Transducer

Vane Motor Autostart Vane Motor Switch
Switch Open

MON. 10:00 AM Starter Motor Current >15% for 10
Malfunction seconds with Control Center
Detected not calling for motor to run.

MON. 10:00 AM Program Initiated Autostart Microboard
Reset

Replace RTC-IC RTC-IC Chip
Chip Reprogram
Setpoints

MON. 10:00 AM Low Oil Autostart Oil Temperature 71.0°F 55°F
Temperature Thermistor (RT3)

MON. 10:00 AM Faulty Discharge Discharge Temp. Thermistor 30.0°F 29.9°F
Temperature (RT2) disconnected or faulty
Sensor (min. system operating
temp. = 32°F)

MON. 10:00 AM Low Line Voltage SSS Logic Board See legend on
(SSS units only) wiring diagram.

MON. 10:00 AM Motor Phase SSS Logic Board See Section 2.
Current Unbalance
(SSS units only)

Troubleshooting