16 electrical data cooling/electric heat, W/ direct drive dee036 – York SUNLINE PLUS D1EE036 User Manual

Page 17

Advertising
background image

036-21411-002-A-0204

Unitary Products Group

17

TABLE 16: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ DIRECT DRIVE DEE036

MODEL

DEE

POWER

SUPPLY

HEATER

ACCESSORY

MODEL

NUMBER

SUPPLY

AIR

BLOWER

MOTOR

FLA

ELECTRIC HEATERS

MINIMUM

CIRCUIT

AMPACITY

MAX

FUSE
SIZE

1

AMPS

MAX.

SIZE

HACR

2

kW

STAGES

TOTAL

AMPS

036

208-1-60

2CE04500506

4.4

4.0

1

19.1

30.7

45

45

2CE04500706

5.6

1

27.1

39.4

45

45

2CE04501006

8.0

1

38.3

53.4

60

60

2CE04501506

11.9

2

57.4

77.3

80

80

2CE04502006

15.9

2

76.6

101.2

110

110

230-1-60

2CE04500506

4.4

5.3

1

22.1

33.1

45

45

2CE04500706

7.5

1

31.3

44.6

45

45

2CE04501006

10.6

1

44.2

60.7

70

70

2CE04501506

15.9

2

66.0

88.3

90

90

2CE04502006

21.2

2

88.3

115.9

125

125

208-3-60

2CE04500525

3

4.4

4.0

1

11.0

24.3

35

35

2CE04500725

3

5.6

1

15.6

25.0

35

35

2CE04501025

8.0

1

22.1

33.1

35

35

2CE04501525

11.9

2

33.1

46.9

50

50

2CE04502025

15.9

2

44.2

60.7

70

70

230-3-60

2CE04500525

3

4.4

5.3

1

12.7

24.3

35

35

2CE04500725

3

7.5

1

18.0

28.1

35

35

2CE04501025

10.6

1

25.5

37.4

40

40

2CE04501525

15.9

2

38.2

53.3

60

60

2CE04502025

21.2

2

51.0

69.2

70

70

460-3-60

2CE04500746

3

2.2

6.8

1

8.2

13.0

15

15

2CE04501046

3

10.1

1

12.1

17.9

20

20

2CE04501546

3

13.6

1

16.4

23.2

25

25

2CE04502046

3

19.5

2

23.5

32.1

35

35

575-3-60

2CE04501058

2.2

10.6

1

10.2

15.5

20

20

2CE04501558

15.9

1

15.3

21.9

25

25

2CE04502058

21.2

2

20.4

28.2

30

30

1.

Dual element, time delay type.

2.

Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.

3.

These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), the following fuse
block accessories are available for field installation (see Table 19).

Advertising