Figure 11 - unit dimensions deg 3, 4, & 5 ton, Table 24: dee/deg unit clearances, 11 unit dimensions deg 3, 4, & 5 ton – York SUNLINE PLUS D1EE036 User Manual

Page 25: 24 dee/deg unit clearances

Advertising
background image

036-21411-002-A-0204

Unitary Products Group

25

Note:

DEE Models and ductwork are approved for zero
clearance to combustible materials when equipped
with electric heaters.

Note:

EG Models must have a 1” clearance between any
combustible material and the supply air ductwork for
a distance of 3 feet from the unit.

The products of combustion must not be allowed to accumu-
late within a confined space and recirculate. Locate unit so
that the vent air outlet hood is at least:

Three feet above any forced air inlet located within 10
horizontal feet (excluding those integral to the unit).

Four feet below, 4 horizontal feet from, or 1 foot above
any door or gravity air inlet into the building.

Four feet from electric meters, gas meters, regulators
and relief equipment.

FIGURE 11 -UNIT DIMENSIONS DEG 3, 4, & 5 TON

DEG UNITS

3-5 TON

TABLE 24: DEE/DEG UNIT CLEARANCES

FRONT

DEE UNITS

24”

DEG UNITS

32”

BACK

12” (Less Economizer)

36” (With Economizer or

Fixed Air/Motorized

Damper)

LEFT SIDE (Filter Access)

24” (Less Economizer)

36” (With Economizer)

RIGHT SIDE (Cond. Coil)

24”

BELOW UNIT

1

1.

Units may be installed on combustible floors made from
wood or class A, B, or C roof covering material.

0”

ABOVE UNIT

2

2.

Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.

72” (For Condenser Air

Discharge)

R E T U R N A I R

S U P P L Y A I R

O U T D O O R A I R

O U T D O O R A I R

( E c o n o m i z e r )