OPTIONAL OUTDOOR AIR

(Shall be made available by either/or):

1. ELECTRONIC ENTHALPY AUTOMATIC ECONO-

MIZER - Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring-
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55 ºF. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully
close on power loss.

2. DUAL INPUT DIFFERENTIAL ELECTRONIC

ENTHALPY AUTOMATIC ECONOMIZER - Outdoor and
return air dampers that are interlocked and positioned by
a fully-modulating, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake damp-
ers shall not exceed 2% when dampers are fully closed
and operating against a pressure differential of 0.5 IWG.
A unit mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take in
the design CFM of outdoor air to meet the minimum ven-
tilation requirement of the conditioned space during nor-
mal operation. During economizer operation, a mixed-air
temperature control shall modulate the outdoor and
return air damper assembly to prevent the supply air
temperature from dropping below 55 ºF. Changeover
from compressor to economizer operation shall be pro-
vided by two integral electronic enthalpy controls - one
that senses outdoor air and one that senses indoor air.
Both enthalpy sensors supply input to the logic module
which modulates both sets of dampers for maximum
economizer savings. The outdoor intake opening shall
be covered with a rain hood that matches the exterior of
the unit. Water eliminator/filters shall be provided. Simul-
taneous economizer/compressor operation is also possi-
ble. Dampers shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAIL-

ABLE

1. ROOF CURB - 14" AND 8" high, full perimeter knock-

down curb with hinged design for quick assembly.

2. MANUAL OUTDOOR DAMPER - Provides 0% through

35% or 0% through 100% outdoor air capability (field
adjustable). Designed for duct mounted side supply/
return applications. Includes a hood and a screen
assembly.

3. OUTDOOR COIL GUARD - Prevents coil damage.

4. BAROMETRIC RELIEF DAMPER - Contains a rain

hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.

5. PROPANE CONVERSION KIT - Contains new orifices

and gas valve regulator to convert from natural to L.P.
gas.

6. LOW NOX - Required to reduce the emission of nitrogen

oxides below 40 nano grams per joule.

7. HIGH ALTITUDE - NATURAL GAS - Required for appli-

cations between 2000 and 6000 feet altitude.

8. HIGH ALTITUDE - PROPANE GAS - Required for appli-

cations between 2000 and 6000 feet altitude. Must be
used with propane conversion kit.

9. GAS PIPING - Contains pipe nipples, fittings and gas

cock (including panel assess gaskets) required for bot-
tom gas supply connection with external shut-off.

10. BURGLAR BARS - Designed to work with above

roofcurbs. Fits duct openings of curb supply and return
air openings.

11. THERMOSTATS - Multiple models available from

A.C.O., M.C.O., Electronic or Electrical Mechanical ver-
sions.

12. ANTI-RECYCLE TIMER - Assures 5-minute off-time

between compressor cycles.

13. LOW AMBIENT KIT - Provides unit cooling operation

down to 0 ºF.

14. ELECTRIC HEAT - Slide-in design, provides single point

power and ranges from 5 to 30 KW.

OTHER FACTORY INSTALLED OPTIONS

1. HIGH PERFORMANCE BELT DRIVE MOTOR

2. TECHNICOAT PHENOLIC COATED COND. COIL

3. ELECTRONIC ENTHALPY ECONOMIZER

4. DUAL INPUT ELECTRONIC ENTHALPY ECONO-

MIZER