Fan coil unit saphir, 8 to 3.5 kw, Technical features – York SAPHIR CMR00 User Manual

Page 2

Advertising
background image

E-COM-H0703

Fan Coil Unit SAPHIR

0.8 to 3.5 kW

(1) Room temperature 27°C d.b., 19ºC w.b. - Water temperature 7/12 °C
(2) Room temperature 20°C - Water inlet temperature: 50°C
(3) Room temperature 20°C - Water inlet temperature: 70/60°C
(4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s.
* Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Technical features

Model

130

140

230

240

Total cooling capacity [kW]

(1)

max

1.50

2.00

2.87

3.52

med

1.14

1.54

2.39

3.00

min

0.83

1.13

1.86

2.29

Sensible cooling capacity [kW]

(1)

max

1.16

1.58

2.16

2.70

med

0.86

1.19

1.78

2.27

min

0.62

0.85

1.37

1.70

Water flow in cooling [l/h]

(1)

max

282

342

493

605

med

197

264

410

515

min

143

197

319

394

Pressure drop in cooling [kPa]

(1)

max

1.9

2.9

7.0

10.1

med

0.9

1.7

5.1

7.6

min

0.5

0.9

3.2

4.7

Heating capacity 2 pipes [kW]

(2)

max

1.98

2.79

3.83

4.82

med

1.49

2.07

3.21

4.05

min

1.09

1.48

2.50

3.07

Water flow in heating 2 pipes [l/h] *

(2)

max

282

342

493

605

med

197

264

410

515

min

143

197

319

394

Pressure drop in heating 2 pipes [kPa]

(2)

max

1.6

2.4

5.8

8.4

med

0.7

1.4

4.2

6.3

min

0.4

0.7

2.7

3.9

Heating capacity 2 pipes [kW]

(3)

max

3.81

5.10

6.56

8.21

med

2.84

3.91

5.44

6.89

min

2.09

2.83

4.23

5.20

Water flow in heating 2 pipes [l/h]

(3)

max

333

450

574

718

med

248

342

476

602

min

183

247

370

455

Pressure drop in heating 2 pipes [kPa]

(3)

max

2.1

4.1

7.2

10.7

med

1.1

2.3

5.1

7.8

min

0.6

1.1

3.3

4.7

Heating capacity 4 pipes [kW]

(3)

max

1.94

2.36

3.28

3.73

med

1.59

1.97

2.92

3.38

min

1.25

1.59

2.48

2.84

Water flow in heating 4 pipes [l/h]

(3)

max

170

206

287

326

med

139

172

256

296

min

109

139

217

248

Pressure drop in heating 4 pipes [kPa]

(3)

max

2.2

3.3

10.4

13.2

med

1.5

2.3

8.5

11.0

min

0.9

1.5

6.3

8.0

Air flow [m3/h]

max

275

390

425

550

med

201

288

330

460

min

125

190

246

325

Sound power level [dB(A)]

max

44

53

48

55

med

36

45

43

50

min

28

35

35

41

Sound pressure level [dB(A)]

(4)

max

35

44

39

46

med

27

36

34

41

min

19

26

26

32

Power supply [V-ph-Hz]

230 - 1- 50

Power input [W]

max

31

42

61

63

Absorbed current [W]

max

0.14

0.20

0.29

0.28

Water content (2 pipes) [l]

0.96

0.96

1.40

1.40

Advertising