ELECTRICAL DATA

RSH/RSV ELECTRICAL DATA

Unit Size

SUPPLY

VOLTAGE

COMPRESSOR

BLOWER

MIN. CCT.

AMPACITY

MAX FUSE /

CCT. BKR. AMP

QTY

RLA

LRA

HP

FLA

007

208-230/1/60

1

@

3.4

22.0

0.10

0.8

5.05

15

009

208-230/1/60

1

@

4.6

28.0

0.10

0.8

6.55

15

012

208-230/1/60

1

@

5.6

29.0

0.13

1.0

8.00

15

265/1/60

1

@

4.6

20.0

0.13

0.9

6.65

15

018

208-230/1/60

1

@

6.9

48.0

0.17

1.4

10.03

15

265/1/60

1

@

6.1

44.0

0.17

0.8

8.43

15

024

208-230/1/60

1

@

8.2

48.0

0.25

1.5

11.75

15

265/1/60

1

@

7.0

44.0

0.25

1.3

10.05

15

208-230/3/60

1

@

6.1

58.0

0.25

1.3

8.93

15

030

208-230/1/60

1

@

10.1

60.0

0.33

2.6

15.23

25

265/1/60

1

@

8.7

58.0

0.33

1.9

12.78

20

208-230/3/60

1

@

7.2

58.0

0.33

2.6

11.60

15

036

208-230/1/60

1

@

13.5

83.0

0.50

3.2

20.08

30

265/1/60

1

@

11.6

79.0

0.50

2.2

16.70

25

208-230/3/60

1

@

8.7

78.0

0.50

3.2

14.08

20

460/3/60

1

@

4.3

40.0

0.50

2.5

7.88

15

042

208-230/1/60

1

@

19.9

109.0

0.50

3.2

28.08

45

208-230/3/60

1

@

13.6

81.0

0.50

3.2

20.20

30

460/3/60

1

@

6.1

41.0

0.50

2.5

10.13

15

575/3/60

1

@

4.2

33.0

0.50

1.8

7.05

15

048

208-230/1/60

1

@

23.1

144.0

0.75

4.9

33.78

50

208-230/3/60

1

@

16.0

91.0

0.75

4.9

24.90

40

460/3/60

1

@

7.1

46.0

0.75

2.2

11.08

15

575/3/60

1

@

5.6

37.0

0.75

1.8

8.80

15

060

208-230/1/60

1

@

26.3

134.0

1.00

5.1

37.98

60

208-230/3/60

1

@

15.6

110.0

1.00

5.1

24.60

40

460/3/60

1

@

7.8

52.0

1.00

3.2

12.95

20

575/3/60

1

@

5.8

38.9

1.00

2.6

9.85

15

070

208-230/3/60

1

@

19.0

123.0

1.00

5.1

28.85

45

460/3/60

1

@

9.7

62.0

1.00

3.2

15.33

25

575/3/60

1

@

7.4

50.0

1.00

2.6

11.85

15

Advertising