Multipliers for determining the performance with other indoor sections.

HEATING PERFORMANCE DATA

CONDENSING UNIT MODEL NO

YHJD30S21S1

EVAPORATOR COIL MODEL NO

AHP30

AIR TEMP.

ENTERING

OUTDOOR UNIT

AIR TEMP.

ENTERING

INDOOR COIL

ID CFM

800

1000

1200

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

60

60

35.2 4.14 2.49 36.8 4.38 2.46 38.3 4.59 2.44

70

33.8 3.80 2.62 35.4 4.00 2.60 36.9 4.20 2.58

80

32.5 3.46 2.75 34 3.63 2.74 35.5 3.82 2.72

47

60

29.3 3.69 2.32 29.9 3.75 2.33 30.6 3.81 2.35

70

28 3.39 2.42 28.7 3.43 2.46 29.4 3.46 2.50

80

26.7 3.10 2.52 27.5 3.11 2.59 28.3 3.12 2.65

40

60

25.8 3.38 2.23 26.8 3.50 2.24 27.7 3.59 2.26

70

24.5 3.12 2.30 25.5 3.22 2.32 26.4 3.30 2.35

80

23.3 2.86 2.38 24.3 2.95 2.41 25.2 3.02 2.44

30

60

21.1 2.97 2.08 21.7 3.01 2.11 22.4 3.05 2.15

70

19.8 2.72 2.13 20.4 2.76 2.17 21.1 2.80 2.21

80

18.5 2.47 2.19 19.2 2.51 2.24 19.9 2.55 2.28

17

60

14.8 2.29 1.89 15.2 2.29 1.94 15.7 2.31 1.99

70

13.5 2.09 1.89 13.9 2.08 1.95 14.4 2.10 2.01

80

12.2 1.89 1.89 12.7 1.88 1.97 13.2 1.89 2.04

10

60

11.3 1.84 1.79 11.9 1.88 1.85 12.5 1.90 1.92

70

10.2 1.68 1.78 10.7 1.70 1.84 11.2 1.72 1.90

80

9.2 1.52 1.77 9.6 1.53 1.83 10 1.54 1.89

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

MBH

KW

COP

FC/MC/PC/UC32

1.00 1.00 1.00

FC/MC/PC/UC35

1.00 1.00 1.00

FC/MC/PC/UC37

1.00 1.00 1.00

FC/MC/PC/UC43

1.00 1.00 1.00

HC36

1.00 1.00 1.00

HC42

1.00 1.00 1.00

HD36

1.00 1.00 1.00

MH240S

1.00 1.00 1.00

MH30S

1.00 1.00 1.00

AHP36

1.00 1.00 1.00

AV36

0.97 1.07 0.93

FPFP040

1.00 1.00 1.00

MV12B

FC/MC35B

0.97 1.06 0.94

MV16C

FC/MC35C

0.97 1.06 0.94

MA12B

FC/MC35B

1.00 1.00 1.00

MV12B

FC/MC43B

0.97 1.05 0.95

MV16C

FC/MC43C

0.97 1.06 0.94

MA12B

FC/MC43B

1.00 1.00 1.00

Variable Speed
Furnace

Coil

MBH

KW

COP

PV8*A12

FC/MC/PC/UC32A 0.98 1.03 0.97

PV9*A12

FC/MC/PC/UC32A 0.98 1.03 0.97

PV8*B16

FC/MC/PC/UC35B 0.97 1.06 0.94

PV8*C16

FC/MC/PC/UC35C 0.97 1.06 0.94

PV8*C20

FC/MC/PC/UC35C 0.98 1.03 0.97

P(C,V)9*B12

FC/MC/PC/UC35B 0.97 1.04 0.96

P(C,V)9*C16

FC/MC/PC/UC35C 0.97 1.05 0.95

PV8*A12

FC/MC/PC/UC37A 0.98 1.03 0.97

PV9*A12

FC/MC/PC/UC37A 0.98 1.03 0.97

PV8*B16

FC/MC/PC/UC43B 0.97 1.06 0.94

PV8*C16

FC/MC/PC/UC43C 0.97 1.06 0.94

PV8*C20

FC/MC/PC/UC43C 0.98 1.03 0.97

P(C,V)9*B12

FC/MC/PC/UC43B 0.97 1.05 0.95

P(C,V)9*C16

FC/MC/PC/UC43C 0.97 1.05 0.95

PV8*B16

HC36 0.97

1.06

0.94

P(C,V)9*B12

HC36 0.97

1.04

0.96

PV8*C16

HC42 0.97

1.06

0.94

PV8*C20

HC42 0.98

1.03

0.97

P(C,V)9*C16

HC42 0.97

1.05

0.95