Table 5: cooling capacity dm078 (6-1/2 ton) unit – York PREDATOR DM 078 User Manual

Page 13

Advertising
background image

246645-YTG-C-0708

Johnson Controls Unitary Products

13

TABLE 5: COOLING CAPACITY DM078 (6-1/2 TON) UNIT

Air On

Evap. Coil

Temperature of Air on Condenser Coil 85°F

Temperature of Air on Condenser Coil 95°F

CFM

WB
(°F)

Tot.

Cap.

*

(MBH)

Tot.

Input

†

(kW)

Sensible Capacity (MBH)

*

Return Dry Bulb (°F)

Tot.

Cap.

*

(MBH)

Tot.

Input

†

(kW)

Sensible Capacity (MBH)

*

Return Dry Bulb (°F)

86

83

80

77

74

71

68

86

83

80

77

74

71

68

1950

72 87

6.8

49

43

37

32

26

-

-

78

7.3

45

40

34

28

23

-

-

67 80

6.7

61

55

50

44

38

33

27

73

7.1

57

52

46

41

35

29

24

62 71

6.4

71

66

61

55

50

44

39

63

6.9

63

61

56

50

45

39

33

57 66

6.4

66

66

61

56

50

44

39

59

6.8

59

59

54

49

43

37

32

2275

72 91

6.9

54

47

41

34

28

-

-

82

7.4

50

44

37

31

24

-

-

67 83

6.7

67

61

54

47

41

34

28

76

7.2

64

57

51

44

38

31

24

62 74

6.5

74

72

66

60

53

47

40

66

6.9

66

65

61

55

48

42

35

57 69

6.5

69

69

67

60

54

47

40

62

6.9

62

62

60

53

46

40

33

2600

72 94

7.0

59

52

44

37

29

-

-

86

7.5

56

48

41

33

26

-

-

67 87

6.8

74

66

58

51

43

36

28

80

7.3

70

63

55

48

40

33

25

62 77

6.6

77

77

72

64

57

49

42

69

7.0

69

69

67

59

52

44

37

57 72

6.6

72

72

72

65

57

49

42

65

7.0

65

65

65

57

50

42

35

2925

72 95

7.0

63

55

46

37

29

-

-

85

7.5

60

51

43

34

25

-

-

67 88

6.8

78

70

61

52

44

35

26

79

7.3

74

66

58

49

40

32

23

62 77

6.6

77

77

75

66

58

49

40

69

7.1

69

69

67

59

50

42

33

57 73

6.6

73

73

73

64

56

47

38

64

7.0

64

64

64

56

47

39

30

3250

72 96

7.0

67

58

48

38

29

-

-

85

7.5

64

54

44

35

25

-

-

67 89

6.8

83

73

64

54

44

35

25

78

7.3

78

70

60

50

41

31

21

62 78

6.6

78

78

78

68

59

49

39

68

7.1

68

68

68

58

49

39

29

57 74

6.6

74

74

74

64

54

45

35

64

7.1

64

64

64

54

45

35

25

Temperature of Air on Condenser Coil 105°F

Temperature of Air on Condenser Coil 115°F

1950

72 73

7.8

43

37

31

26

20

-

-

67

8.3

40

35

29

23

18

-

-

67 66

7.5

54

48

43

37

32

26

21

58

7.9

51

45

40

34

29

23

17

62 64

7.4

61

57

52

46

41

35

30

66

7.9

59

54

48

42

37

31

26

57 54

7.3

54

54

48

43

37

32

26

48

7.8

48

48

43

37

31

26

20

2275

72 76

7.9

48

41

34

28

21

-

-

69

8.4

45

38

32

25

18

-

-

67 68

7.6

60

54

47

40

34

27

21

60

8.0

56

50

43

37

30

24

17

62 67

7.5

65

62

57

50

44

37

31

67

8.0

64

59

52

46

39

33

26

57 56

7.4

56

56

53

46

40

33

27

49

7.9

49

49

46

40

33

27

20

2600

72 78

8.0

53

45

38

30

22

-

-

71

8.4

49

42

34

27

19

-

-

67 71

7.7

66

59

51

44

36

28

21

61

8.1

61

55

47

39

32

24

17

62 69

7.5

69

67

62

54

47

39

31

69

8.0

69

64

57

49

42

34

26

57 58

7.5

58

58

58

50

42

35

27

50

7.9

50

50

50

43

35

28

20

2925

72 78

8.0

57

48

40

31

23

-

-

71

8.5

54

46

37

28

20

-

-

67 70

7.7

68

62

54

46

37

28

20

62

8.2

62

58

51

42

33

25

16

62 69

7.6

69

68

64

56

47

38

30

69

8.1

69

67

61

53

44

35

27

57 58

7.5

58

58

58

49

40

32

23

51

8.0

51

51

51

42

33

25

16

3250

72 78

8.1

61

52

42

32

23

-

-

71

8.6

59

49

40

30

20

-

-

67 70

7.8

70

66

57

48

38

28

19

62

8.3

62

62

55

45

35

25

16

62 69

7.6

69

69

67

57

48

38

28

70

8.2

70

70

66

56

46

37

27

57 57

7.6

57

57

57

48

38

28

19

51

8.1

51

51

51

41

31

22

12

Temperature of Air on Condenser Coil 125°F

1950

72

62

8.8

38

32

27

21

15

-

-

67

51

8.4

48

42

37

31

25

20

14

62

67

8.4

57

50

44

39

33

27

22

57

42

8.3

42

42

37

31

26

20

15

2275

72

63

8.8

42

35

29

22

16

-

-

67

52

8.4

52

46

40

33

27

20

13

62

68

8.5

63

56

48

41

35

28

22

57

43

8.3

43

43

40

33

27

20

14

2600

72

63

8.9

46

39

31

23

16

-

-

67

52

8.5

52

50

43

35

28

20

12

62

69

8.5

69

62

52

44

37

29

21

57

43

8.4

43

43

43

35

28

20

13

2925

72

64

9.0

52

43

34

26

17

-

-

67

53

8.6

53

53

47

39

30

21

13

62

70

8.6

70

66

58

50

41

32

24

57

44

8.5

44

44

44

35

26

18

9

3250

72

65

9.1

57

47

38

28

18

-

-

67

54

8.7

54

54

52

42

32

23

13

62

71

8.8

71

71

65

55

45

36

26

57

44

8.6

44

44

44

34

25

15

5

*

These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air
blower motor.

†

These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.