Specifications – York UL R134A User Manual

Page 4

Advertising
background image

JOHNSON CONTROLS

4

Specifications

POWER AND ELECTRICAL

• Johnson Controls has over 25 years of experience

designing variable speed drives specifically for chiller

applications. The result is an extremely reliable air

cooled chiller system that offers industry leading ef-

ficiency at real world operating conditions, valve-less

compressor loading/unloading, excellent capacity

control, high power factor and soft start.

• All controls and motor starting equipment necessary

for unit operation shall be factory wired and function

tested.

• VSD Power/Control Panel includes main power

connection(s), VSD and fan motor contactors, cur-

rent overloads, and factory wiring. Standard design

includes NEMA 3R (IP55) rating, powder painted steel

cabinet with hinged, latched, and gasket sealed outer

doors equipped with wind struts for safer servicing.

• VSD section of power panel includes a dedicated

inverter for each compressor.

• The panel includes control display access door so

display and control features can be accessed without

opening main cabinet doors.

• Two and three compressor models come standard with

single point power connection. In addition, all models

are supplied with a factory mounted and wired control

transformer that will supply all unit control voltage from

the main unit power supply. The transformer utilizes

scheduled line voltage on the primary side and pro-

vides 115V/1Ø on secondary.

• The standard power panel is equipped with terminal

block electrical connections at the point of incoming

power. An optional factory mounted circuit breaker is

available, at point of incoming single point connection,

that provides the means to disconnect power and short

circuit protection. The optional lockable operating

handle extends through the power panel door so that

power may be disconnected without opening any panel

doors.

• Short Circuit Withstand Rating of the chiller electri-

cal enclosure is 30,000 Amps for standard terminal

block connection. Ratings IAW (in accordance with)

UL508. (See Accessories and Options section: Can

be increased to 65,000 Amps for 380, 400 & 460V).

• Compressor motors are powered by a variable speed

drive. Therefore, motor current never exceeds the

rated load amps (RLA), providing soft starts with no

electrical inrush. This eliminates the motor heating

and stress always found with conventional motor

starters. In addition, by eliminating the heat build up

during starting, the required off-time between starts is

reduced to a maximum of two minutes.

• Many utility companies charge an additional fee

if power factor is below 0.95. These power factor

adjustments/penalties can affect both regular tariff

rates, as well as demand charges. All YCIV models

have a full load power factor of 95% and maintain this

level throughout the operating range. Specifications

should always require the installing contractor to be

responsible for additional cost to furnish and install

power factor correction capacitors if they are not fac-

tory mounted and wired.

S E M I - H E R M E T I C Y O R K T W I N S C R E W

COMPRESSORS
Johnson Controls Engineered Systems’ Chiller Design

Team has developed a world class compressor with un-

equaled performance:
• Continuous function, microprocessor controlled, VSD

provides valveless, smooth capacity control from 100%

down to 10% of chiller capacity for two compressor

chillers and 100% down to 7.5% for three compressor

chillers. In addition, elimination of the slide valve and

associated unloading components resulted in a 50%

reduction in compressor moving parts.

• Compressors are direct drive, semihermetic, rotary

twin-screw type, including: muffler, temperature ac-

tuated ‘off-cycle’ heater, rain-tight (IP55) terminal

box, discharge shut-off service valve, and precision

machined cast iron housing mounted on neoprene

isolators.

• Reliable suction gas cooled, high efficiency, acces-

sible hermetic compressor motor, full suction gas flow

through 0.006” maximum mesh screen, with inherent

internal thermal overload protection and external cur-

rent overload on all three phases.

• Suction gas screen and serviceable, 0.5 micron full

flow oil filter within the compressor housing.

• Cast iron compressor housing precisely machined

for optimal clearances and superb efficiency. Entire

compressor, from suction to discharge has a Design

Working Pressure of 350 PSIG (24 bar) or higher.

REFRIGERANT CIRCUIT

• Independent refrigerant circuits per compressor, each

using copper refrigerant pipe formed on computer

controlled bending machines. This eliminates over

60% of system piping brazed joints as compared to

designs that use fittings, resulting in a highly reliable

and leak resistant system.

• Liquid line components include: liquid line shut-off

valve with charging port, low side pressure relief de-

vice, high adsorption removable core filter-drier, sight

glass with moisture-indicator, and electronic expansion

valve.

Advertising