Each person installing or using this equipment must read and understand the

information in these User Instructions before use. Installation of this equipment by

untrained or unqualified persons, or use that is not in accordance with these User

Instructions may adversely affect product performance and

result in sickness or

death. For proper use see User Instructions or call 3M in U.S.A., 1-800-243-4630.

In Canada, call Technical Service at 1-800-267-4414.

The GD-2A is an electronic detector of combustible gases. The GD-2A is designed

for connection to UL Listed Fire Alarm/Burglary Control Panels. This combustible

gas detector has been evaluated by UL for methane (natural) and propane (LP) gas.

It is NOT designed to detect smoke, fire or carbon monoxide. Once the GD-2A is

operational (ARMED) the green light will be on continuously. If gas is detected the red

LED (ALARM) turns on and the alarm relay activates to indicate the alarm condition at

the control panel. In the configuration, as shipped from the factory, the GD-2A is self-

restoring meaning that when the air clears of gas, the red light turns off and the relay

switches to its normal state.
If you suspect a gas leak, alert others and have everyone leave immediately.

Do not light a match. Do not turn lights on or off. Do not use any electrical

switches, including a garage door opener. Do not use the telephone,

including cell phones. The electrical current in a phone, light or electric

switch is enough to spark an explosion.

Go outside to a safe place away from the suspect area and only then call

the gas company for help or in an emergency call 911.

Stay away from your home until someone in authority tells you it is safe to

return.

GENERAL SAFETY INFORMATION
INTENDED USE
The GD-2A is a low voltage (12-24 VAC or VDC) electronic detector of combustible,

heating type gases. The GD-2A is designed for connection to UL Listed Fire Alarm/

Burglary Control Panels. NOTE: Any time the words “Control Panel” or “Alarm Panel”

or “Alarm Control Panel” are used in these instructions, they refer to a UL Listed

Fire Alarm/Burglary Control Panel. Alarm control panels that work on 12 or 24 VDC

can provide battery backup to the GD-2A detectors. This combustible gas detector

has been evaluated by UL for methane (natural gas) and propane (LP) gas. It is NOT

designed to detect smoke, fire or carbon monoxide.
LIST OF WARNINGS AND CAUTIONS

Each person using this equipment must read and understand the

information in these User Instructions before use. Use of this equipment

by untrained or unqualified persons, or use that is not in accordance with

these User Instructions, may adversely affect product performance and

result in sickness or death.

• Use only for monitoring the gas which the sensor and detector are

designed to monitor. Failure to do so may result in exposures to gases not

detectable and

cause sickness or death. For proper use, see supervisor

or User Instructions, or call 3M in U.S.A., 1-800-243-4630. In Canada, call

Technical Service at 1-800-267-4414.

• GD-2A may not function effectively below 32ºF (0ºC) or above

120ºF (50ºC). Using the detector outside of this temperature range may

adversely affect product performance and

result in sickness or death.

• This detector helps monitor for the presence and concentration level of

certain specified airborne gases. Misuse may produce an inaccurate reading,

which means that higher levels of the gas being monitored may be present

and could result in overexposure and

cause sickness or death. For proper

use, see supervisor or User Instructions, or call 3M in U.S.A.,

1-800-243-4630. In Canada, call Technical Service at 1-800-267-4414.

• The GD-2A is not designed to measure compliance with Occupational

Safety and Health Administration (OSHA) commercial or industrial standards.

• When the unit is powered up it performs a self-test during which the

green LED light will blink for a period of one and one half to two minutes.

Afterward, the green LED light will turn on continuously to indicate the unit

is in normal operation (ARMED). If the self-test fails or the green LED light

does not turn on continuously do not use. Failure to do so may adversely

affect product performance and

result in sickness or death.

• Immediately exit the environment if there is an alarm condition on the

detector.

Failure to do so may result in sickness or death.

• This detector will only indicate the presence of combustible gas at the

sensor. Combustible gas may be present in other areas. Accommodation

spaces should be well ventilated when household cleaning supplies or

similar contaminants are used.

• Do not cover or obstruct visual alarm LED. Doing so may adversely affect

product performance and

result in sickness or death.

• Do not disassemble unit or attempt to repair or modify any component

of this detector. This detector contains no user serviceable parts, and

substitution of components may adversely affect product performance and

result in sickness or death.

CAUTION

Avoid the use of harsh cleaning materials, abrasives and other organic solvents.

Such materials may permanently scratch the surfaces, damage the sensor,

labels, or instrument housing.

If you have any doubts about the applicability of the equipment to your job

situation, consult an industrial hygienist or call 3M at 1-800-243-4630. In

Canada, call Technical Service at 1-800-267-4414.

3

Macurco

Combustible Gas Detector GD-2

User Instructions for the 3M Macurco™ Combustible Gas Detector GD-2

Important:

These User Instructions are to be provided to the homeowner/end

user upon product installation.

3M Occupational Health and

Environmental Safety Division

3M Center, Building 0235-02-W-70

St. Paul, MN 55144-1000

Printed in U.S.A.

3M and Macurco are trademarks of 3M.

© 2010 3M Company. All rights reserved.

98-0060-0162-6/2

34-8704-8986-0

W

WARNING

W

WARNING

USE INSTRUCTIONS AND LIMITATIONS

Each person using this equipment must read and understand the information

in these User Instructions before use. Use of this equipment by untrained

or unqualified persons, or use that is not in accordance with these User

Instructions, may adversely affect product performance and

result in

sickness or death.

USE FOR
The GD-2A is an electronic detector of combustible, heating type gases (natural gas

and propane), designed for connection to alarm control panels. It can operate on 12

to 24 VDC power from standby or interruptible panel power, or be powered separately.

The GD-2A is intended for installation in buildings in non-hazardous locations such as

residences, retail stores, office buildings, and institutional buildings.

Use only for monitoring the gas which the sensor and detector are designed

to monitor. Failure to do so may result in exposures to gases not detectable

and

cause sickness or death. For proper use, see supervisor or User

Instructions, or call 3M in U.S.A., 1-800-243-4630. In Canada, call Technical

Service at 1-800-267-4414.

DO NOT USE FOR
The GD-2A is NOT intended for use in industrial applications such as refineries,

chemical plants, etc. The GD-2A does NOT detect carbon monoxide. Do NOT mount

the GD-2A in a corner. The GD-2A is designed for connection to UL Listed Fire Alarm/

Burglary Control Panels. Do not connect the GD-2A to Fire Alarm Circuits, or Burglar

Alarm or other signals. The Alarm Control Panel must be dedicated to gas detection or

have alarm devices that provide a distinctive alarm for gas detection. Do NOT mount

the GD-2A in kitchens or bathrooms - alcohols, ammonia, cleaning solvents, paint

thinner, gasoline vapors, and aerosol propellants (aerosol cans such as hair spray

usually contain a combustible gas) may cause nuisance alarms.

GD-2A may not function effectively below 32ºF (0°C) or above 120ºF (50°C).

Using the detector outside of this temperature range may adversely affect

product performance and

result in sickness or death.

GENERAL DESCRIPTION
The GD-2A is a low voltage (12-24 VAC or VDC) electronic detector of combustible,

heating type gases, that has been evaluated by UL for methane (natural gas) and

propane (LP) gas. The GD-2A is designed for connection to UL Listed Fire Alarm/

Burglary Control Panels. The GD-2A has a SPDT Alarm relay, for connection to control

panels or other devices. The GD-2A does NOT detect carbon monoxide. The GD-2A

does not have an internal audible sounder.

FEATURES
• LISTED TO UL STANDARD 2075 FOR THE STANDARD FOR SAFETY FOR GAS AND

VAPOR DETECTOR AND SENSORS

• SENSITIVITY TESTED BASED ON UL 1484 STANDARD FOR RESIDENTIAL GAS

DETECTORS

• DETECTS HEATING GASES: PROPANE (LP), NATURAL GAS (METHANE),
• SPDT ALARM AND N.C. TROUBLE RELAYS
• CAN BE SELF-RESTORING OR LATCHING
• ELECTRONIC SENSORS: NO MAINTENANCE OR RECALIBRATION
• TEMPERATURE COMPENSATED
• SIMPLE INSTALLATION AND OPERATION
• SUPERVISED SENSOR

W

WARNING

W

WARNING

SPECIFICATIONS
• SIZE: 4 1/2 X 5 X 1 5/8 inches
• SHIPPING WEIGHT: 0.54 pound
• VOLTAGE: 12 to 24 VAC or VDC
• CURRENT (non-alarm): 45 mA @ 12 VDC, 22 mA @ 24 VDC, 65 mA

@ 12 VAC, 45 mA @ 24 VAC

• CURRENT (in alarm): 70 mA @ 12 VDC, 35 mA @ 24 VDC, 100 mA

@ 12 VAC, 65 mA @ 24 VAC

• COLOR: White
• SENSOR MAINTENANCE: Not required
• ALARM RELAY: SPDT, 0.125 AMPS, 40V, 3VA
• TROUBLE RELAY: SPST (NC), 0.250 AMPS, 40V, 10VA
• OPERATING TEMPERATURE RANGE: 32°F to 120°F (0°C to 50°C)
• ALARM SET POINT: Per UL 1484 (25% LEL)

INSTALLATION AND OPERATING INSTRUCTIONS
The following instructions are intended to serve as a guideline for the use of the

3M™ Macurco™ GD-2A Combustible Gas Detector. It is not to be considered

all-inclusive, nor is it intended to replace the policy and procedures for each facility.

This detector helps monitor for the presence and concentration level of certain

specified airborne gases. Misuse may produce an inaccurate reading, which

means that higher levels of the gas being monitored may be present and

could result in overexposure and

cause sickness or death. For proper use,

see supervisor or User Instructions, or call 3M in U.S.A., 1-800-243-4630. In

Canada, call Technical Service at 1-800-267-4414.

LOCATION
A GD-2A is usually located in each room (except kitchens or bathrooms) where there

are gas appliances or through which gas pipes pass. Do NOT mount the GD-2A in

a corner. Do NOT mount the GD-2A in kitchens or bathrooms - alcohols, ammonia,

cleaning solvents, paint thinner, gasoline vapors, and aerosol propellants (aerosol

cans such as hair spray usually contain a combustible gas) may cause alarms. Do

NOT mount the GD-2A where the normal ambient temperature is below 32°F (0°C) or

exceeds 120°F (50°C).

This product is intended for use in ordinary indoor locations of family

living units and office workspaces. The GD-2A is not designed to measure

compliance with Occupational Safety and Health Administration (OSHA)

commercial or industrial standards.

INSTALLATION
1. If the gas used is natural gas (methane) mount the GD-2A on a wall about one

foot down from the ceiling. If the gas used is propane (LP), mount the GD-2A on

a wall or column one foot above the floor. Use the same spacing as for smoke

detectors-30 foot centers, 900 square feet per detector.

2. The three part plastic case allows the GD-2A to be either surface mounted or

installed over a four-inch square or double gang electrical box, providing a near

flush mount. The GD-2A snap-on front cover will need to be removed before

installation. To remove it, lightly pry the front cover off of the mounting plate

(middle section) with a coin or flat screwdriver inserted into the vent at the

bottom. The cover will snap off exposing the electronics and mounting plate.

3. For flush mount, remove the 2 screws and rear cover from the mounting plate

and use the appropriate hole pattern for installation. The four holes toward the

center of the mounting plate match the hole pattern of a double gang electrical

box. The four holes near the corners match the pattern of a four-inch square

box. Mount the GD-2A so the “TOP” marked side of the mounting plate is at the

highest side. Snap the front cover back on when finished, making sure that the

lights line up with the access holes.

W