Cooling System Specifications

Table 22

Caterpillar SCA Requirements for SCA and

Water Cooling Systems

Cooling System

Capacity

Caterpillar SCA

at Initial Fill

Caterpillar SCA

at 250 Hours

22 to 30 L

(6 to 8 US gal)

1.75 L (64 fl oz)

0.44 L (15 fl oz)

31 to 38 L

(9 to 10 US gal)

2.30 L (80 fl oz)

0.57 L (20 fl oz)

39 to 49 L

(11 to 13 US gal)

3.00 L (100 fl oz)

0.75 L (25 fl oz)

50 to 64 L

(14 to 17 US gal)

3.90 L (128 fl oz)

0.95 L (32 fl oz)

65 to 83 L

(18 to 22 US gal)

5.00 L (168 fl oz)

1.25 L (42 fl oz)

84 to 110 L

(23 to 29 US gal)

6.60 L (224 fl oz)

1.65 L (56 fl oz)

111 to 145 L

(30 to 38 US gal)

8.75 L (296 fl oz)

2.19 L (74 fl oz)

146 to 190 L

(39 to 50 US gal)

11.50 L

(392 fl oz)

2.88 L (98 fl oz)

191 to 250 L

(51 to 66 US gal)

15.00 L

(512 fl oz)

3.75 L (128 fl oz)

Refer to Table 23 for part numbers and for quantities
of SCA.

Table 23

Caterpillar Liquid SCA

Part Number

Quantity

6V-3542

0.24 L (8 oz)

111-2372

0.36 L (12 oz)

8T-1589

0.47 L (16 oz)

3P-2044

0.94 L (32 oz)

8C-3680

19 L (5 US gal)

5P-2907

208 L (55 US gal)

Maintain the SCA in the same way as you would
maintain a cooling system that uses heavy-duty
coolant/antifreeze. Adjust the maintenance for the
amount of SCA additions. See Table 22 for the
amount of SCA that is required.

Cooling Systems with Larger
Capacities

Adding the SCA to Water at the Initial Fill

Use the equation that is in Table 24 to determine
the amount of Caterpillar SCA that is required at
the initial fill. This equation is for a mixture of only
SCA and water.

Table 24

Equation For Adding The SCA To Water

At The Initial Fill

V × 0.07 = X

V is the total volume of the cooling system.

X is the amount of SCA that is required.

Table 25 is an example for using the equation that
is in Table 24.

Table 25

Example Of The Equation For Adding The SCA

To Water At The Initial Fill

Total Volume

of the Cooling

System (V)

Multiplication

Factor

Amount of SCA

that is Required

(X)

946 L

(250 US gal)

× 0.07

66 L

(18 US gal)

Adding the SCA to Water for Maintenance

For the recommended service interval, refer to the
Operation and Maintenance Manual, “Maintenance
Interval Schedule” for your engine.

Use the 8T-5296 Coolant Conditioner Test Kit to
test the concentration of SCA. Make the following
modifications to Steps 3 and 5 of the 8T-5296
Coolant Conditioner Test Kit instructions:

STEP 3 –

Add tap water to the vial up to the “20

ml” mark.

STEP 5 –

When the defined procedure is used,

a concentration of six to eight percent will yield
between 20 drops and 27 drops. If the number of
drops is below 20 drops, the concentration of SCA
is low. If the number of drops is above 27 drops, the
concentration of SCA is high. Make the appropriate
adjustments to the concentration of SCA.

Test the concentration of SCA or submit a
coolant sample to your Caterpillar dealer. See
this publication, “S·O·S Coolant Analysis” topic
(Maintenance Section).