Duct Smoke Detector
Installation/configuration notes | en
57
Bosch Sicherheitssysteme GmbH
Installation guide
F.01U.033.733 | 5.0 | 2011.11
If in doubt, use an airflow measuring device to measure the air
speed in the duct.
3.2
Installation position
Avoid selecting an installation position near ducts with dead-air
space or areas with turbulence.
Turbulence mainly occurs near connecting flanges, branches,
tight bends, and long, straight ducts.
Place the FAD-420-HS-EN at a distance of at least three times
the width of the ventilation duct [b
≥ 3 x d] away from these
critical areas (see Figure 3.1).
3.3
Housing position
The FAD-420-HS-EN must only be mounted in a vertical or
horizontal position (see Figure 3.2).
Figure 3.2
Position of housing on the ventilation duct
1
2
3
No.
Description
e
Airflow direction