Cycle Applications: Limit initial current to 25.0A. Charge until battery voltage

(under charge) reaches 14.4 to 14.7 volts at 68°F (20°C). Hold at 14.4 to 14.7

volts until current drops to under 1.24A. Battery is fully charged under these

conditions, and charger should be disconnected or switched to “float” voltage.

“Float” or “Stand-By” Service: Hold battery across constant voltage source of

13.5 to 13.8 volts continuously. When held at this voltage, the battery will seek its

own current level and maintain itself in a fully charged condition.

Note: Due to the self-discharge characteristics of this type of battery, it is

imperative that they be charged within 6 months of storage, otherwise permanent

loss of capacity might occur as a result of sulfation.

Chargers

Power-Sonic offers a wide range of chargers suitable for batteries up to 100AH.

Please refer to the Charger Selection Guide in our specification sheets for “C-Series

Switch Mode Chargers” and “Transformer Type A and F Series”. Please contact our

Technical department for advice if you have difficulty in locating suitable models.

®

Further Information

Please refer to our website www.power-sonic.com for a complete range of useful

downloads, such as product catalogs, material safety data sheets (MSDS), ISO

certification, etc..

Constant Current & Power Discharge Ratings

MODEL

FINAL

VOLTAGE

AMPS/WATTS PER CELL @ 25° C

5 MIN

10 MIN

15 MIN

20 MIN

30 MIN

45 MIN

60 MIN

A

W

A

W

A

W

A

W

A

W

A

W

A

W

PG-12V120 FR

1.80

232

598

198

485

172

394

152

330

124

242

90

176

72

143

1.75

265

620

216

510

188

412

167

341

132

258

130

182

72.5

144

1.67

304

635

248

538

216

430

182

352

140

263

96.7

192

74.4

145

1.60

377

658

274

562

224

442

183

360

143

269

99

197

73.5

147

C

ap

ac

ity

R

et

en

tion

R

at

io

(%

)

Standing Period (Months)

100

80

60

40

0

0 2 4 6 8 10 12 14 16 18 20

40

o

C

(104

o

F)

30

o

C

(86

o

F)

20

o

C

(68

o

F)

5

o

C

(41

o

F)

Charging is not

necessary unless

100% of capacity

is required.

Charging before

use is necessary

to help recover

full capacity.

Chargemayfail

to restore full

capacity. Do not

let batteries reach

this state.

Discharge Characteristics

Discharge Time vs. Discharge Current

Shelf Life & Storage

Discharge Current (A)

Discharge T

ime

Discharge Time

Terminal V

oltage (V)

10

9

8
7
6
5

4

3

60

50

40
30
20
10

8

6
4

2 5 7 11

12 14 17 30 50 70 120 240

0

(min

)

(h

)

360 600

2

40°C (104°F)
25°C ( 77°F)

0°C ( 32°F)

Ambient Temperature: 25°C(77°F)

13

12

11

10.8

10.5

9.6

9

7.8

3

5 10

20

30

0

2 3

5

10

20

(min)

(h)

74.4A

32A 21.3A

12.4A 6.48A

120A

60

PG-12V120 

FR

 12 Volt  129 AH 

@ 20-hr. rate

, 124 AH

 @ 10-hr. rate

CORPORATE OFFICE • 7550 Panasonic Way • San Diego, CA 92154 • USA • Tel: +1-619-661-2020 • Fax: +1-619-661-3650

CUSTOMER SERVICE

Tel: +1-619-661-2030

Fax: +1-619-661-3648

[email protected]

INTERNATIONAL SALES

Tel: +1-650-364-5001

Fax: +1-650-366-3662

[email protected]

DOMESTIC SALES

Tel: +1-619-661-2020

Fax: +1-619-661-3650

[email protected]

TECHNICAL SUPPORT

Tel: +1-619-661-2020

Fax: +1-619-661-3648

[email protected]

Contact Information

www.power-sonic.com

0111 1M

© 2011. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners.

Advertising