0 ah, Charging, Chargers – Power-Sonic PDC-121000 User Manual

Page 2: Discharge characteristics, Further information, Ab c, Cycle life in relation to depth of discharge, Contact information, Hr. rate

Advertising
background image

Charging

Cycle Applications:Limitinitialcurrentto27A.Chargeuntilbatteryvoltage

(undercharge)reaches14.4to14.7voltsat68°F(20°C).Holdat14.4to14.7

voltsuntilcurrentdropstounder1000mA.Batteryisfullychargedunderthese

conditions, and charger should be disconnected or switched to “float” voltage.

“Float” or “Stand-By” Service:Holdbatteryacrossconstantvoltagesourceof

13.5 to 13.8 volts continuously. When held at this voltage, the battery will seek its

owncurrentlevelandmaintainitselfinafullychargedcondition.

Note:Duetotheself-dischargecharacteristicsofthistypeofbattery,itis

imperativethattheybechargedwithin6monthsofstorage,otherwisepermanent

lossofcapacitymightoccurasaresultofsulfation.

Chargers

Power-Sonicoffersawiderangeofchargerssuitableforbatteriesupto100AH.

Please refer to the Charger Selection Guide in our specification sheets for “C-Series

Switch Mode Chargers” and “Transformer Type A and F Series”. Please contact our

Technical department for advice if you have difficulty in locating suitable models.

Discharge Characteristics

PDC-121000 12 Volt 100.0 AH

@ 20-hr. rate

, 92.0 AH

@ 10-hr. rate

®

Further Information

Pleaserefertoourwebsitewww.power-sonic.comforacompleterangeofuseful

downloads,suchasproductcatalogs,materialsafetydatasheets(MSDS),ISO

certification, etc..

1

2

4 6 8 10

20

40 60

2

4 6 8 10 20

min

h

4.0

4.5

5.0

5.5

6

6V Battery

(V)

12V Battery

(V)

.0

6.5

0

200 400 600 800 1000 1200 1400 1600 1800

20

40

60

80

100

120

0

-

20

-10

0

10

20

30

40

50

0

20

40

60

80

100

120

0.10CA

0.12 CA

0.21CA

1CA

2CA

3CA

8

10

12

0

4

6

60

80

100

0

2

20

40

A

B

C

0

4

8

12

16

20

24

28

%

(A)

(V/cell)

Terminal V

oltage (V)

Capacity Ratio (%)

Capacity (%)

Remaining Capacity (%)

Temperature(°C)

Temperature: 25°C

Charge

Volume

Charging

Current

Charged

Voltage Charge at 0.1C Amp Initial Charging Current and

2.45V/Cell Constant Voltage at 25°C

Discharge Time

Charging Time (Hours)

Number of Cycles

Storage Time (Months)

A

B

C

10°C

100%

DOD

50%

DOD

30%

DOD

30°C

40°C

No supplementary charge required

(Carry out supplementary charge before use if 100% capacity is required.)

Supplementary charge required before use.Optional charging way as below:

1.Charged for above 3 days at limted current 0.25CA and constant volatge 2.25V/cell.

2.Charged for above 20hours at limted current 0.25CA and constant volatge 2.45V/cell.

3.Charged for 8~10hours at limted current 0.05CA .

Supplementary charge may often fail to recover the capacity.

The battery should never be left standing till this is reached

25°C

Testing condition

Discharging:current 0.17C (FV 1.7V/cell);

Charging:current 2.45V/cell,max. 0.25CA;

Charging volume:125% of discharged capacity.

13.0

12.0

120

0.1C

0.08C

0.06C

0.04C

0.02C

2.5

2.4

2.3

2.2

2.1

0C

100

80

60

40

20

11.0

10.0

9.0

8.0

5.0A

9.0A

19.2A

35A

58.1A

99.0A

186A

340A

Charged Volume

Charge Voltage

(Constant 2.45V/Cell)

After 50% Discharge
After 100% Discharge

Charging Current

(Initial at 0.1C Amp)

1

2

4 6 8 10

20

40 60

2

4 6 8 10 20

min

h

4.0

4.5

5.0

5.5

6

6V Battery

(V)

12V Battery

(V)

.0

6.5

0

200 400 600 800 1000 1200 1400 1600 1800

20

40

60

80

100

120

0

-

20

-10

0

10

20

30

40

50

0

20

40

60

80

100

120

0.10CA

0.12 CA

0.21CA

1CA

2CA

3CA

8

10

12

0

4

6

60

80

100

0

2

20

40

A

B

C

0

4

8

12

16

20

24

28

%

(A)

(V/cell)

Terminal V

oltage (V)

Capacity Ratio (%)

Capacity (%)

Remaining Capacity (%)

Temperature(°C)

Temperature: 25°C

Charge

Volume

Charging

Current

Charged

Voltage Charge at 0.1C Amp Initial Charging Current and

2.45V/Cell Constant Voltage at 25°C

Discharge Time

Charging Time (Hours)

Number of Cycles

Storage Time (Months)

A

B

C

10°C

100%

DOD

50%

DOD

30%

DOD

30°C

40°C

No supplementary charge required

(Carry out supplementary charge before use if 100% capacity is required.)

Supplementary charge required before use.Optional charging way as below:

1.Charged for above 3 days at limted current 0.25CA and constant volatge 2.25V/cell.

2.Charged for above 20hours at limted current 0.25CA and constant volatge 2.45V/cell.

3.Charged for 8~10hours at limted current 0.05CA .

Supplementary charge may often fail to recover the capacity.

The battery should never be left standing till this is reached

25°C

Testing condition

Discharging:current 0.17C (FV 1.7V/cell);

Charging:current 2.45V/cell,max. 0.25CA;

Charging volume:125% of discharged capacity.

13.0

12.0

120

0.1C

0.08C

0.06C

0.04C

0.02C

2.5

2.4

2.3

2.2

2.1

0C

100

80

60

40

20

11.0

10.0

9.0

8.0

5.0A

9.0A

19.2A

35A

58.1A

99.0A

186A

340A

Charged Volume

Charge Voltage

(Constant 2.45V/Cell)

After 50% Discharge
After 100% Discharge

Charging Current

(Initial at 0.1C Amp)

1

2

4 6 8 10

20

40 60

2

4 6 8 10 20

min

h

4.0

4.5

5.0

5.5

6

6V Battery

(V)

12V Battery

(V)

.0

6.5

0

200 400 600 800 1000 1200 1400 1600 1800

20

40

60

80

100

120

0

-

20

-10

0

10

20

30

40

50

0

20

40

60

80

100

120

0.10CA

0.12 CA

0.21CA

1CA

2CA

3CA

8

10

12

0

4

6

60

80

100

0

2

20

40

A

B

C

0

4

8

12

16

20

24

28

%

(A)

(V/cell)

Terminal V

oltage (V)

Capacity Ratio (%)

Capacity (%)

Remaining Capacity (%)

Temperature(°C)

Temperature: 25°C

Charge

Volume

Charging

Current

Charged

Voltage Charge at 0.1C Amp Initial Charging Current and

2.45V/Cell Constant Voltage at 25°C

Discharge Time

Charging Time (Hours)

Number of Cycles

Storage Time (Months)

A

B

C

10°C

100%

DOD

50%

DOD

30%

DOD

30°C

40°C

No supplementary charge required

(Carry out supplementary charge before use if 100% capacity is required.)

Supplementary charge required before use.Optional charging way as below:

1.Charged for above 3 days at limted current 0.25CA and constant volatge 2.25V/cell.

2.Charged for above 20hours at limted current 0.25CA and constant volatge 2.45V/cell.

3.Charged for 8~10hours at limted current 0.05CA .

Supplementary charge may often fail to recover the capacity.

The battery should never be left standing till this is reached

25°C

Testing condition

Discharging:current 0.17C (FV 1.7V/cell);

Charging:current 2.45V/cell,max. 0.25CA;

Charging volume:125% of discharged capacity.

13.0

12.0

120

0.1C

0.08C

0.06C

0.04C

0.02C

2.5

2.4

2.3

2.2

2.1

0C

100

80

60

40

20

11.0

10.0

9.0

8.0

5.0A

9.0A

19.2A

35A

58.1A

99.0A

186A

340A

Charged Volume

Charge Voltage

(Constant 2.45V/Cell)

After 50% Discharge
After 100% Discharge

Charging Current

(Initial at 0.1C Amp)

1

2

4 6 8 10

20

40 60

2

4 6 8 10 20

min

h

4.0

4.5

5.0

5.5

6

6V Battery

(V)

12V Battery

(V)

.0

6.5

0

200 400 600 800 1000 1200 1400 1600 1800

20

40

60

80

100

120

0

-

20

-10

0

10

20

30

40

50

0

20

40

60

80

100

120

0.10CA

0.12 CA

0.21CA

1CA

2CA

3CA

8

10

12

0

4

6

60

80

100

0

2

20

40

A

B

C

0

4

8

12

16

20

24

28

%

(A)

(V/cell)

Terminal V

oltage (V)

Capacity Ratio (%)

Capacity (%)

Remaining Capacity (%)

Temperature(°C)

Temperature: 25°C

Charge

Volume

Charging

Current

Charged

Voltage Charge at 0.1C Amp Initial Charging Current and

2.45V/Cell Constant Voltage at 25°C

Discharge Time

Charging Time (Hours)

Number of Cycles

Storage Time (Months)

A

B

C

10°C

100%

DOD

50%

DOD

30%

DOD

30°C

40°C

No supplementary charge required

(Carry out supplementary charge before use if 100% capacity is required.)

Supplementary charge required before use.Optional charging way as below:

1.Charged for above 3 days at limted current 0.25CA and constant volatge 2.25V/cell.

2.Charged for above 20hours at limted current 0.25CA and constant volatge 2.45V/cell.

3.Charged for 8~10hours at limted current 0.05CA .

Supplementary charge may often fail to recover the capacity.

The battery should never be left standing till this is reached

25°C

Testing condition

Discharging:current 0.17C (FV 1.7V/cell);

Charging:current 2.45V/cell,max. 0.25CA;

Charging volume:125% of discharged capacity.

13.0

12.0

120

0.1C

0.08C

0.06C

0.04C

0.02C

2.5

2.4

2.3

2.2

2.1

0C

100

80

60

40

20

11.0

10.0

9.0

8.0

5.0A

9.0A

19.2A

35A

58.1A

99.0A

186A

340A

Charged Volume

Charge Voltage

(Constant 2.45V/Cell)

After 50% Discharge
After 100% Discharge

Charging Current

(Initial at 0.1C Amp)

Cycle Life in Relation to Depth of Discharge

1

2

4 6 8 10

20

40 60

2

4 6 8 10 20

min

h

4.0

4.5

5.0

5.5

6

6V Battery

(V)

12V Battery

(V)

.0

6.5

0

200 400 600 800 1000 1200 1400 1600 1800

20

40

60

80

100

120

0

-

20

-10

0

10

20

30

40

50

0

20

40

60

80

100

120

0.10CA

0.12 CA

0.21CA

1CA

2CA

3CA

8

10

12

0

4

6

60

80

100

0

2

20

40

A

B

C

0

4

8

12

16

20

24

28

%

(A)

(V/cell)

Terminal V

oltage (V)

Capacity Ratio (%)

Capacity (%)

Remaining Capacity (%)

Temperature(°C)

Temperature: 25°C

Charge

Volume

Charging

Current

Charged

Voltage Charge at 0.1C Amp Initial Charging Current and

2.45V/Cell Constant Voltage at 25°C

Discharge Time

Charging Time (Hours)

Number of Cycles

Storage Time (Months)

A

B

C

10°C

100%

DOD

50%

DOD

30%

DOD

30°C

40°C

No supplementary charge required

(Carry out supplementary charge before use if 100% capacity is required.)

Supplementary charge required before use.Optional charging way as below:

1.Charged for above 3 days at limted current 0.25CA and constant volatge 2.25V/cell.

2.Charged for above 20hours at limted current 0.25CA and constant volatge 2.45V/cell.

3.Charged for 8~10hours at limted current 0.05CA .

Supplementary charge may often fail to recover the capacity.

The battery should never be left standing till this is reached

25°C

Testing condition

Discharging:current 0.17C (FV 1.7V/cell);

Charging:current 2.45V/cell,max. 0.25CA;

Charging volume:125% of discharged capacity.

13.0

12.0

120

0.1C

0.08C

0.06C

0.04C

0.02C

2.5

2.4

2.3

2.2

2.1

0C

100

80

60

40

20

11.0

10.0

9.0

8.0

5.0A

9.0A

19.2A

35A

58.1A

99.0A

186A

340A

Charged Volume

Charge Voltage

(Constant 2.45V/Cell)

After 50% Discharge
After 100% Discharge

Charging Current

(Initial at 0.1C Amp)

Charging Characteristics (Cycle Use)

Temperature Effects in Relation to Battery Capacity

Self Discharge Characteristics

CORPORATE OFFICE • 7550 Panasonic Way • San Diego, CA 92154 • USA • Tel: +1-619-661-2020 • Fax: +1-619-661-3650

CUSTOMER SERVICE

Tel:+1-619-661-2030

Fax:+1-619-661-3648

[email protected]

INTERNATIONAL SALES

Tel: +1-650-364-5001

Fax: +1-650-366-3662

[email protected]

DOMESTIC SALES

Tel:+1-619-661-2020

Fax: +1-619-661-3650

[email protected]

TECHNICAL SUPPORT

Tel:+1-619-661-2020

Fax:+1-619-661-3648

[email protected]

Contact Information

www.power-sonic.com

1012 1M

© 2012. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners.