144 ah, Charging, Chargers – Power-Sonic PG-12V140 User Manual

Page 2: Further information, Constant current & power discharge ratings, Hr. rate, Contact information

Advertising
background image

Charging

Cycle Applications: Limit initial current to 25.0A. Charge until battery voltage

(under charge) reaches 14.4 to 14.7 volts at 68°F (20°C). Hold at 14.4 to 14.7

volts until current drops to under 1.44A. Battery is fully charged under these

conditions, and charger should be disconnected or switched to “float” voltage.

“Float” or “Stand-By” Service: Hold battery across constant voltage source of

13.5 to 13.8 volts continuously. When held at this voltage, the battery will seek its

own current level and maintain itself in a fully charged condition.

Note: Due to the self-discharge characteristics of this type of battery, it is

imperative that they be charged within 6 months of storage, otherwise permanent

loss of capacity might occur as a result of sulfation.

Chargers

Power-Sonic offers a wide range of chargers suitable for batteries up to 100AH.

Please refer to the Charger Selection Guide in our specification sheets for “C-Series

Switch Mode Chargers” and “Transformer Type A and F Series”. Please contact our

Technical department for advice if you have difficulty in locating suitable models.

®

Further Information

Please refer to our website www.power-sonic.com for a complete range of useful

downloads, such as product catalogs, material safety data sheets (MSDS), ISO

certification, etc..

Constant Current & Power Discharge Ratings

MODEL

FINAL

VOLTAGE

AMPS/WATTS PER CELL @ 25° C

5 MIN

10 MIN

15 MIN

20 MIN

30 MIN

45 MIN

60 MIN

A

W

A

W

A

W

A

W

A

W

A

W

A

W

PG-12V140 FR

1.80

270

604

231

490

200

410

177

342

144

286

104

208

84

165

1.75

309

628

252

532

219

435

195

378

154

303 113.5 214

84.9

167

1.67

354

654

289

568

252

478

213

385

163

306

113

218

84

168

1.60

440

675

319

625

260

486

214

396

161

309

112

223

85.7

170

C

ap

ac

ity

R

et

en

tion

R

at

io

(%

)

Standing Period (Months)

100

80

60

40

0

0 2 4 6 8 10 12 14 16 18 20

40

o

C

(104

o

F)

30

o

C

(86

o

F)

20

o

C

(68

o

F)

5

o

C

(41

o

F)

Charging is not

necessary unless

100% of capacity

is required.

Charging before

use is necessary

to help recover

full capacity.

Chargemayfail

to restore full

capacity. Do not

let batteries reach

this state.

Discharge Characteristics

Discharge Time vs. Discharge Current

Shelf Life & Storage

Discharge Current (A)

Discharge T

ime

Discharge Time

Terminal V

oltage (V)

Ambient Temperature: 25°C(77°F)

10

9

8
7
6
5

4

3

60

50

40
30
20
10

8

6
4

7 8 9 13 14.4 18 20 40 60 92 144 310

0

(min

)

(h

)

460 820

2

40°C (104°F)
25°C ( 77°F)

0°C ( 32°F)

13

12

11

10.8

10.5

9.6

9

7.8

3

5 10

20

30

0

2 3

5

10

20

(min)

(h)

84A

36.4A 24.1A

14.4A 7.7A

140A

60

PG-12V140 

FR

 12 Volt  154 AH 

@ 20-hr. rate

, 144 AH

 @ 10-hr. rate

CORPORATE OFFICE • 7550 Panasonic Way • San Diego, CA 92154 • USA • Tel: +1-619-661-2020 • Fax: +1-619-661-3650

CUSTOMER SERVICE

Tel: +1-619-661-2030

Fax: +1-619-661-3648

[email protected]

INTERNATIONAL SALES

Tel: +1-650-364-5001

Fax: +1-650-366-3662

[email protected]

DOMESTIC SALES

Tel: +1-619-661-2020

Fax: +1-619-661-3650

[email protected]

TECHNICAL SUPPORT

Tel: +1-619-661-2020

Fax: +1-619-661-3648

[email protected]

Contact Information

www.power-sonic.com

0111 1M

© 2011. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners.