5.2 Electric Lock Connection

5.2.1 Door Lock Controlled with Internal Power

connect one lock

connect two locks

Note:

1. Electronic lock of Power-on-to-unlock type should be used.
2. The door lock is limited to 12V, and holding current must be less than 250mA.
3. The door lock control is not timed from Exit Button(EB).
4. The

Unlock Mode

Parameter of Monitor must be set to 0 (by default).

EB

*

LOCK

BUS

PL

S1+

S2+

S-

LOCK

2

nd

1

ST

2

nd

EB

*

1

ST

Jumper position in

Connect two locks

1-2

EB

*

LOCK

BUS

PL

S1

+

S2

+

S-

Jumper position in

Connect one lock

1-2

5.2.2 Door Lock Controlled with Dry Contact

Note:

1. The external power supply must be used according to the lock.
2. The jumper must be taken off before connecting.
3. Setup the

Unlock Mode

of Monitor for different lock types.

• Power-on-to-unlock type:Unlock Mode=0 (by default)
• Power-off-to-unlock type:Unlock Mode=1