The most important adjustment steps – VEGA D81 METEC Hydrostatic pressure transmitter User Manual
Page 27

Pressure transmitter D81 METEC
®
27
Setup
The most important adjustment steps
On the following four pages, you see a menu
schematic of the HART
®
handheld in conjunc-
tion with pressure transmitters D80 … D87.
The most important adjustment steps are
marked in the menu schematic with the letters
A … D. If you are not familiar with HART
®
handheld, please note:
After entering a parameter, first push the
"
ENTER" key. The adjustment is saved in the
handheld, but not in the sensor itself.
After you have pushed "
ENTER", you have to
push "
SEND" (here in the example for the
min. adjustment), to transfer the input to the
sensor.
After pushing "
SEND", a message is dis-
played warning you that you are about to
change device output and for safety rea-
sons, you should switch your system to
manual operation. Push "
OK" and the adjust-
ment is now transferred to the sensor.
After a moment, you are asked to switch the
system from manual to automatic operation.
Confirm with "
OK"
and then with "
HOME".
4.1
(5.1)
Empty adjustment without
medium
You are now in the initial menu.
Generic: SENSOR
PV LVR
0.000 mbar
10.000
mbar
HELP DEL
ESC ENTER
Generic: SENSOR
1 PV
LRV
2 PV
URV
HELP SEND
HOME
Generic: SENSOR
– WARNING –
Pressing „OK“ will
change device output
Put loop in manual
ABORT OK
Generic: SENSOR
Online (general)
1 Sensor unit
2 PV
80.945 mbar
3 PV Analog output
4 PV LRV
5 PV URV
HELP
SAVE
Generic: SENSOR
1 PV
LRV
2 PV
URV
HELP
HOME
Generic: SENSOR
– WARNING –
Return control loop to
automatic control
OK