3 functional table – VEGA VEGAKON 63 User Manual

Page 11

Advertising
background image

VEGAKON

11

4.3 Functional table

The following table shows the switching conditions dependent on the adjusted mode and level.

Level

Switching condition

Switching condition

Signal lamp

Relay module E60 R

Transistor module E60 T

VEGAKON

Mode A

Relay energized

Transistor conductive

light off

Maximum
monitoring
or overfill

protection

Relay de-energized

Transistor blocks

light on

Mode B

Relay energized

Transistor conductive

light off

Minimum

monitoring
or protection
against dry
running of
pumps

Relay de-energized

Transistor blocks

light on

Power failure

Mode

Relay de-energized

Transistor blocks

light off

A/B

Note

If VEGAKON is used for oil warning in water, the electrode must be cleaned after responding to oil (empty signal)
as otherwise reset to water is not reliably guaranteed.