Electrical connection, Cu-line, Vessel with cathodic corrosion protection – VEGA VEGASWING 83 fail safe and signal conditioning instrument VEGATOR 526 Ex User Manual
Page 21

VEGASWING 81 W5 Ex.C, 83 W5 Ex.C fail safe
21
Electrical connection
E2
E1
A2
A1
A1
A2
E2
E1
1
2
Typ
B62-27
Typ
B62-27G
d30
d32
E86 Ex
Overvoltage
arrester
min. 4 mm
2
Cu
Screen
optionally
overvoltage arrester
Note:
- Use suitable cable, optionally with metal cover or screen. Screen or metal cover must only be
connected to the overvoltage arrester. Screen or metal cover must not be earthed.
- The cable must have an outer isolation.
- The capacity of the screen must at least correspond to that of a 1,5 mm
2
Cu-line.
Earth / PA
connection terminal
Outer
isolation
Vessel with cathodic corrosion protection
Screen
Line length
≤
␣ 50 m
Metal housing
isolated mounted or
plastic housing
Overvoltage arrester
type B62 - 27 Ex 0
or B62 - 27 Ex
Outer
isolation
External
earth
terminal
Cathodic tank protection
2 … 24 V
(object voltage)
VEGASWING
VEGATOR
526 Ex
Ex-area
Not Ex-area
(control room)