Pressure transmitter D96/D97 (Profibus PA)
If you want to carry out the "Adjustment tak-
ing the actual product into account" (live
adjustment), click in this window to
yes
, then
to
OK
.
Setup
Here you can choose in which unit the adjust-
ment should be made (mbar or bar, psi, kPa,
inHg). Then you enter the pressure values
corresponding to 0 % and 100 %. Then click
to
OK
. The adjustment is now finished.
Click to
Min-Adjustment
or to
Max-Adjust-
ment
to carry out the respective adjustment.
Note:
For min. adjustment and max. adjustment,
defined levels (e.g. 0 % and 100 % or e.g.
20 % and 80 %) have to be present in the
vessel.
In the window "Min-Adjustment" you choose in
which unit the adjustment should be carried
out (bar, mbar, psi, kPa, inHg). Then click to
Save
. The min. adjustment is finished.
In the window "Max-Adjustment" you choose
in which unit the adjustment should be car-
ried out (bar, mbar, psi, kPa, inHg). Then
click to
Save
. The max. adjustment is fin-
ished.
Sensor parameter setting – Linearisa-
tion curves
Click in the window "Instrument data param-
eter adjustment" to
Conditioning
.