3 mounting steps external housing – VEGA VEGABAR 65 4 … 20 mA_HART User Manual
Page 14
S
eal the flange connections according to DIN/ANSI with a suitable,
resistant seal and mount VEGABAR 65 with suitable screws.
U
se the seal suitable for the respective process fitting. You can find
the components in the supplementary instructions manual "Welded
socket and seals".
4.3 Mounting steps external housing
1
M
ark the holes according to the following drilling template
2
D
epending on the mounting surface, fasten the wall mounting
plate with 4 screws
90 mm (3.54")
R 3,5 mm
(0.14")
3mm
(0.12")
70 mm (2.76")
8 mm
(0.32")
93 mm (3.66")
110 mm (4.33")
Fig. 5: Drilling template - wall mounting plate
Tip:
M
ount the wall mounting plate so that the cable entry of the socket
housing points downward. The socket housing can be displaced by
180°
to the wall mounting plate.
Warning:
T
he four screws of the socket housing must only be hand-screwed. A
torque > 5 Nm (3.688 lbf ft) can damage the wall mounting plate.
Sealing/Screwing in
flange versions
Sealing/Screwing in hy-
gienic fittings
Wall mounting
14
VEGABAR
65 • 4 … 20
mA/HART