Pressure transmitter D84
Instrument modification
Installation procedure:
• Place the new form seal (5) over the meas-
uring cell (the conical end must point to the
process connection!).
• Carefully insert pressure transmitter into
the process connection by turning clock-
wise.
• Tighten hexagon pressure screw (4) (width
across flats, 46 mm) (45 Nm).
• Turn the housing (1) of the pressure
transmitter to the original position.
The exchange of the form seal is now fin-
ished; the removed seal must be properly
disposed of.
1 Pressure transmitter
2 Headless screw (prevents overwinding and must not be
removed)
3 Adapter
4 Hexagon screw
5 Form seal
6 Process connection
1
2
3
4
5
6