VEGA VEGACAL 63 Profibus PA User Manual
Page 40
40
10 Supplement
VEGACAL 63 • Profibus PA
30028-EN-130917
Max. torque (process fitting - thread) -
rod: ø 10 mm (0.394 in)
100 Nm (73 lbf ft)
Max. torque (process fitting - thread) -
rod: ø 16 mm (0.63 in)
100 Nm (73 lbf ft)
Output variable
Output signal
digital output signal, format according to IEEE-754
Sensor address
126 (default setting)
Current value
10 mA, ±0.5 mA
Damping (63 % of the input variable)
0 … 999 s, adjustable
Input variable
Measured variable
Level of liquids
Measuring principle
phase-selective admittance processing (PSA)
Measuring range
0 … 3000 pF
Measuring frequency
270 kHz
Accuracy (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ Relative humidity
45 … 75 %
Ʋ Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Temperature error
Ʋ < 120 pF
< 1 pF
Ʋ > 120 pF
1 % of the current measured value
Linearity error
< 0.25 % of the complete measuring range
Ambient conditions
Ambient, storage and transport tempera-
ture
-40 … +80 °C (-40 … +176 °F)
Process conditions
Process pressure
Ʋ Threaded versions
-1 … 64 bar/-100 … 6400 kPa (-14.5 … 928 psig), de-
pending on the process fitting
Ʋ Flange version
-1 … 64 bar/-100 … 6400 kPa (-14.5 … 928 psig), de-
pending on the process fitting
Ʋ Flange version ≥ 3"/DN 80, plated
-0.4 … 64 bar/-40 … 6400 kPa (-5.8 … 928 psig), de-
pending on the process fitting
Process temperature VEGACAL 63 of 316L
Ʋ Insulation PE
-40 … +80 °C (-40 … +176 °F)
Ʋ Insulation PTFE
-50 … +150 °C (-58 … +302 °F)