5 menu schematic, Basic adjustment, Reset – VEGA VEGACAL 64 4 … 20 mA_HART - two-wire User Manual
Page 29
29
6 Set up with the display and adjustment module PLICSCOM
VEGACAL 64 • 4 … 20 mA/HART - two-wire
30030-EN-130917
Basic adjustment
If the function "Reset" is carried out, the sensor resets all settings to
default.
The following values will be reset:
Function
Reset value
Max. adjustment
3000 pF
Min. adjustment
0 pF
Damping ti
0 s
Linearization
Linear
Sensor-TAG
Sensor
Display
%
Current output - characteristics
4 … 20 mA
Current output - max. current
20.5 mA
Current output - min. current
3.8 mA
Current output - failure
< 3.6 mA
Special parameters
All special parameters are reset to delivery status.
Peak value
The min. and max. values are reset to the actual value.
6.5 Menu schematic
Basic adjustment
▶
Basic adjustment
1
Display
Diagnostics
Service
Info
Min. adjustment
1.1
0.00 %
=
0.0 pF
82.5 pF
Max. adjustment
1.2
100.00 %
=
1000.0 pF
327.4 pF
Damping
1.3
0 s
Linearization curve
1.4
Linear
Sensor-TAG
1.5
Sensor
Reset