The menu item "Extended setting" offers the possibility to optimise
VEGAPULS
61 for applications in which the level changes very
quickly. For this reason, select the function "Quick level change > 1 m/
min.".
Extended setting
quick level change > 1 m/min.
Note:
Since with the function "Quick level change > 1 m/min." the generation
of an average value of the signal processing is considerably reduced,
false reflections by agitators or vessel installations can cause
measured value fluctuations. A false echo memory is thus recom-
mended.
This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".
The following data are read out or written with this function:
l
Measured value presentation
l
Adjustment
l
Medium
l
Standpipe inner diameter
2)
l
Vessel form
l
Damping
l
Linearisation curve
l
Sensor-TAG
l
Displayed value
l
Scaling unit (Out-Scale unit)
l
Positions after the decimal point (scaled)
l
Scaling PA/Out-Scale 4 values
l
Unit of measurement
l
Language
The following safety-relevant data are not read out or written:
l
Sensor address
l
PIN
Copy sensor data
Copy sensor data?
2)
With standpipe versions.
Extended setting/Quick
level change
Copy sensor data
42
VEGAPULS
61 • Profibus PA
6 Set up with the indicating and adjustment module PLICSCOM