VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual
Page 51
-
Average power
< 5 µW
-
Average power with 1 m distance
< 200
nW/cm
2
Max. emitted HF power of the antenna system - Version with increased sensitivity
-
Pulse peak power
< 10
mW
-
Pulse duration
< 2
ns
-
Average power
< 25 µW
-
Average power with 1 m distance
< 1 µW/
cm
2
Measuring accuracy
Resolution, general
max. 1 mm (0.039 in)
Deviation
7)
see diagrams
0,5 m (1.6 ft)
20 m (65.62 ft)
10 mm (0.394 in)
3 mm (0.116 in)
- 3 mm (- 0.116 in)
- 10 mm (- 0.394 in)
0
Fig. 32: Deviation VEGAPULS 63
1,0 m (3.280 ft)
20 m (65.62 ft)
30 mm (1.180 in)
15 mm (0.590 in)
- 15 mm (- 0.590 in)
- 30 mm (- 1.180 in)
0
Fig. 33: Deviation VEGAPULS 63 with increased sensitivity in mm, measuring range in m
Influence of the ambient temperature to the sensor electronics
8
)
7)
Incl. non-linearity, hysteresis and non-repeatability.
8)
Relating to the nominal measuring range, in the temperature range
-40 … +80 °C .
VEGAPULS
63 • Foundation Fieldbus
51
10 Annex
28451
-
EN
-120530