17

5 Connecting to power supply

VEGASWING 63 • - transistor (NPN/PNP)

29230-EN-130409

We recommend connecting VEGASWING 63 in such a way that the

switching circuit is open when there is a level signal, line break or

failure (safe condition).
The instrument is used to control relays, contactors, magnet valves,

warning lights, horns as well as PLC inputs.
Caution:

There is no reverse polarity protection. Take note of the polarity of the

output lines.

+

-

1 2 3 4

+

-

Fig. 12: NPN action

+

-

1 2 3 4

+

-

Fig. 13: PNP action

5.4 Wiring plan - version IP 66/IP 68, 1 bar

1

2

3

4

5

Fig. 14: Wire assignment connection cable. The numbers of the wires corre-

spond to the terminals of the instrument.
1 brown (+) voltage supply

2 White

3 Yellow

4 blue (-) voltage supply

5 Shielding

Wiring plan

Wire assignment, con-

nection cable