Scaling, Current output, Unit of measurement – VEGA VEGAFLEX 66 (-110…+400°C) 4 … 20 mA_HART - four-wire User Manual

Page 31: Language, Hart mode, Sensor length/sensor type, Gating out of false signals, The following values will be reset

Advertising
background image

l

S

caling

l

C

urrent output

l

U

nit of measurement

l

L

anguage

l

S

ensitivity

T

he following safety-relevant data are not read out or written:

l

HART

mode

l

PIN

l

SIL

l

S

ensor length/Sensor type

l

G

ating out of false signals

C

opy sensor data

C

opy sensor data?

Basic adjustment
I

f the function "Reset" is carried out, the sensor resets the

values of the following menu items to the reset values (see
chart):

1)

T

he following values will be reset:

Function

Reset value

M

ax. adjustment

D

istance, upper dead zone

M

in. adjustment - Rod/Coax version

D

istance, supplied sensor length

M

in. adjustment - Cable version

D

istance, lower dead zone

I

ntegration time ti

0

s

L

inearisation

linear

S

ensor-TAG

S

ensor

D

isplay

D

istance

C

urrent output - characteristics

4 … 20

mA

C

urrent output - max. current

20

mA

C

urrent output - min. current

4

mA

C

urrent output - failure

<

3.6

mA

A

pplication - rod/coax version

L

iquid

A

pplication - Cable version

S

olid

T

he values of the following menu items are not reset to the

reset values (see chart) with "Reset":

1)

S

ensor-specific basic adjustment.

Reset

VEGAFLEX

66 • 4 … 20

mA/HART - four-wire

31

6 S

et up with the indicating and adjustment module PLICSCOM