4 recurring function test – VEGA VEGAWAVE 62 - NAMUR User Manual
Page 21
Level
Signal current -
Sensor
Control lamp
Falling characteris-
tics max.
≥
2.4 mA
Falling characteris-
tics max.
≤
1 mA
Rising characteris-
tics min.
≥
2.4 mA
Rising characteris-
tics min.
≤
1 mA
Malfunction
any
≤
1 mA
flashes
6
.4 Recurring function test
According to IEC 61508.
VEGAWAVE
62 is qualified in mode A (overfill protection) for use in
measuring chains of stage SIL2 according to IEC 61508 (redundant,
stage SIL3).
The following instrument combinations meet the requirements
according to SIL:
VEGAWAVE
62
l
Oscillator WE60N
The recurring test according to IEC 61508 can be carried out by
pushing the simulation key on the electronics module or by briefly (> 2
seconds) interrupting the cable to the sensor. The correct sequence of
the switching conditions must be monitored via the switching amplifier
as well as the connected systems. The sensor must neither be
removed nor response must be triggered by filling the vessel. This
applies to VEGAWAVE 62 with NAMUR electronics module WE60N.
SIL
Recurring function test
VEGAWAVE
62 • - NAMUR
21