5 Connecting to power supply
VEGACAP 67 • - transistor (NPN/PNP)
31316-EN-130916
4
5
6
3
2
1
Fig. 10: Electronics and connection compartment
1 Potentiometer for switching point adaptation
2 DIL switch for measuring range selection
3 DIL switch for mode adjustment
4 Ground terminal
5 Connection terminals
6 Control lamp
We recommend connecting VEGACAP 67 in such a way that the
switching circuit is open when there is a level signal, line break or
failure (safe condition).
The instrument is used to control relays, contactors, magnet valves,
warning lights, horns as well as PLC inputs.
Caution:
There is no reverse polarity protection. Take note of the polarity of the
output lines.