VEGA VEGAPULS 66 (≥ 2.0.0 - ≤ 3.8) enamel Profibus PA User Manual
Page 20
Advertising
100%
0%
1
> 500 mm
Fig. 13: VEGAPULS 66 in a bypass tube. The polarisation marking on the
process fitting must be in one plane with the tube holes or the tube connection
openings.
1
Marking of the polarisation direction
When the sensor is mounted on a bypass tube, the distance from
VEGAPULS
66 to the upper tube connection should be approx.
500 mm (19.69 in) or more. In case of extremely rough tube inner
walls, you should use an inserted tube (tube in tube) or a radar sensor
with tube antenna.
Information:
With VEGAPULS 66 in flange version, the polarisation plane is always
in the center between two flange holes.
20
VEGAPULS
66 enamel • Profibus PA
4 Mounting
33335
-EN
-090305