VEGA VEGACAP 67 - Relay (DPDT) User Manual

Page 30

Advertising
background image

30

9 Supplement

VEGACAP 67 • - Relay (DPDT)

31315-EN-130916

Supporting tube length L1

0.2 … 5.6 m (0.656 … 18.37 ft)

Max. lateral load

10 Nm (7.4 lbf ft)

Max. tensile load (cable)

Ʋ Ceramic partly insulated: ø 8 mm

(0.315 in)

10 KN (2248 lbf)

Max. torque (process fitting - thread)

80 Nm (58 lbf ft)

Measuring frequency

430 kHz

Output variable
Output

Relay output (DPDT), 2 floating spdts

Switching voltage

Ʋ Min.

10 mV

Ʋ Max.

253 V AC, 253 V DC
With circuits > 150 V AC/DC, the relay contacts must be

in the same circuit.

Switching current

Ʋ Min.

10 µA

Ʋ Max.

3 A AC, 1 A DC

Breaking capacity

Ʋ Min.

50 mW

Ʋ Max.

750 VA AC, 54 W DC
If inductive loads or stronger currents are switched

through, the gold plating on the relay contact surface will

be permanently damaged. The contact is then no longer

suitable for switching low-level signal circuits.

Contact material (relay contacts)

AgNi (Au plated) or AgSnO (Au plated)

Modes (switchable)

Min./Max.

Switching delay

Ʋ When immersed

0.7 s

Ʋ When laid bare

0.7 s

Ʋ In case of failure

1 s

Ambient conditions
Ambient temperature on the housing

-40 … +80 °C (-40 … +176 °F)

Storage and transport temperature

-40 … +80 °C (-40 … +176 °F)

Process conditions
Process pressure

-1 … 16 bar/-100 … 1600 kPa (-14.5 … 232 psig)

Process temperature (thread or flange temperature)

Ʋ Standard

-50 … +300 °C (-58 … +572 °F)

Ʋ with external housing

-50 … +400 °C (-58 … +752 °F)

Advertising