3 function chart – VEGA VEGACAP 69 - contactless electronic switch User Manual
Page 20
20
6 Setup
VEGACAP 69 • - contactless electronic switch
31174-EN-130916
5. Turn the potentiometer (1) very slowly clockwise until the control
lamp (6) lights red. If the control lamp does not light red, set the
meas. range selection switch (2) to the next higher stage and
repeat the setting with the potentiometer (1) until the control lamp
lights red.
The measuring system is now ready for operation.
6.3 Function chart
The following chart provides an overview of the switching conditions
depending on the set mode and the level.
Level
Switching status Control lamp
Mode max.
Overflow protec-
tion
2
1
Switch closed
Green
Mode max.
Overflow protec-
tion
2
1
Switch open
Red
Mode min.
Dry run protection
2
1
Switch closed
Green
Mode min.
Dry run protection
2
1
Switch open
Red
Failure of the sup-
ply voltage
(min./max. mode)
any
2
1
Switch open
Fault
any
2
1
Switch open
flashes red