VEGA VEGABAR 63 Profibus PA User Manual
Page 52
Output variable
Output signal
digital output signal, format according to IEEE-754
Sensor address
126 (default setting)
Current value
10 mA, ±0.5 mA
Dynamic behaviour output
Run-up time approx.
10 s
90 %
100 %
10 %
t
t
T
A
t
t
S
2
1
Fig. 28: Sudden change of the process variable, dead time t
T
, rise time t
A
and step response time t
S
1
Process variable
2
Output signal
Dead time
≤
150 ms
Rise time
≤
100 ms (10 … 90 %)
Step response time
≤
250 ms (ti: 0 s, 10 … 90 %)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Input variable
Adjustment
Adjustment range of the min./max. adjustment relating to the nominal measuring range:
-
Min.
-5 … +95 %
-
Max.
-5 … +105 %
Adjustment range of the zero/span adjustment relating to the nominal measuring range:
-
zero
-5 … +95 %
-
Span
-5 … +105 %
Recommended max. turn down
10 : 1 (no limitation)
Nominal measuring ranges and overload resistance
52
VEGABAR
63 • Profibus PA
10 Supplement
32463
-EN
-081209