3 wiring plan – VEGA VEGABAR External housing User Manual
Page 11
![background image](/manuals/263329/11/background.png)
11
5 Connect the sensor to the external housing
External housing • For pressure transmitter VEGABAR
31087-EN-130322
5. Connect the wire ends as described in chapter "Connection plan".
Take note of the numbering.
6. Connect the screen to the internal ground terminal, connect the
outer ground terminal to potential equalisation
7. Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
8. Attach the mounting plate again and tighten the screws
The electrical connection of the sensor to the external housing is
finished.
You find the electrical connection of the electronics module in chapter
"Wiring plan" or in the operating instructions manual of the respetive
sensor.
5.3 Wiring plan
Fig. 7: External housing in conjunction with VEGABAR 51, 52, 53, 54, 55
Overview - VEGABAR
series 50